Herunterladen Inhalt Inhalt Diese Seite drucken

Balluff BNI CIP-351-000-K015 Betriebsanleitung Seite 313

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BNI CIP-351-000-K015
Safe I/O Module, EtherNet/IP™ CIP Safety™
IP67 Module
17. At this step, the SNCT is performing verification to know if:
a. The module is locked
b. The module has no password protection
18. If the module is locked, click on Unlock Device button
19. If the module is protected by a password, enter it and select OK. If the password is unknown, go to the
section
Reset Password
20. The Safety Reset service is successful.
21. Power OFF the module
22. Go Offline and Exit SNCT
Note!
After a Safety Reset, the safety module is configured as follow:
State: Waiting for TUNID
Lock State: False
IP Address: DHCP or Static (according the rotary switches position)
Note!
The safety reset service can also be performed using Rockwell Logix5000 / Studio5000
software.
Got to the module safety properties dialog box and select the Safety tab.
www.balluff.com
137

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis