Safe I/O Module, EtherNet/IP™ CIP Safety™
IP67 Module
Safety No Pulse Test - The output is used without pulse test.
M12 pining and wiring of the safety sourcing outputs:
1: 24 VDC (powered from UL)
2: Safe Output #1 (OUT1)
3: Ground Output (UL GND)
4: Safe Output #0 (OUT0)
5: Ground Output (UL GND)
Note!
The maximum current available on the Pins #1 (24 VDC) of the 2 Output sourcing ports
is 3.5A.
www.balluff.com
Notes!
Safety Sourcing outputs should not be used to provide power to a device
or sub-system whom the resistive and capacitive load could vary during
operation.
Warning!
Be careful of the response time of the output device to prevent any malfunction
because of pulse test.
Note!
In this mode, diagnostics are done on the output. When a sourcing output is
switched off, the measured state can be different to the expected one due to the
capacitive load of the connected equipment. The Safe I/O Module have been
designed to control a wide range of equipment by using an active discharge
circuit. When a sourcing output is switched off, if a residual voltage is present, a
50mA current is clamped during 2ms.
External Load
1
2
24V
5
OUT1
1
GND
OUT0
GND
4
3
External Load