Herunterladen Inhalt Inhalt Diese Seite drucken

Balluff BNI CIP-351-000-K015 Betriebsanleitung Seite 233

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BNI CIP-351-000-K015
Safe I/O Module, EtherNet/IP™ CIP Safety™
IP67 Module
Safe Output status LEDs (Ox)
LED State
Safety
Output
Status
OFF
Good
YELLOW
Good
RED
Fault
BLINKING
Fault
RED
Link and Network Activity Status LEDs (LINK)
LED State
Speed
Negotiate
OFF
BLINKING
GREEN
100 Mbps
GREEN
BLINKING
YELLOW
10 Mbps
YELLOW
Module Status LED (MOD)
LED State
Speed
Negotiate
OFF
No power
GREEN
Executing
BLINKING
Idle state
GREEN
Critical
RED
Fault
BLINKING
Self-test
RED
www.balluff.com
Description
Output is OFF, or module being configured
Output is ON
A fault in the output circuit has been detected, or values received from network for
the two outputs used as dual output pair are different.
A fault in the other output circuit has been detected (whatever the output mode
configuration: single or dual) or unrecoverable detected faults affecting all outputs
of the module.
Description
No network link.
Link is established with no activity.
Link is established with activity.
Link is established with no activity.
Link is established with activity.
Description
No power applied to the device.
The device is operating in a normal condition.
The device is in the Idle or Standby State.
The device has an unrecoverable fault, may need replacing.
The device is in Self-Test or the device needs commissioning due to configuration
or TUNID missing, incomplete or incorrect.
57