BNI CIP-351-000-K015
Safe I/O Module, EtherNet/IP™ CIP Safety™
IP67 Module
Update
9
Firmware
Stored
Address
a
(all other
rotary
positions)
Note!
The rotary switch position is ONLY read at the boot of the Safe I/O Module. Any
modification of the position will require a power cycle (ON  OFF  ON) of the module.
www.balluff.com
9
9
b
c
Note!
Module sends request indefinitely.
Note!
In this mode, it is not possible to store
an IP address using CIP Explicit
messages (0xF5 TCP/IP Object).
The module enters in the update FPGA and
firmware mode.
Note!
Please contact Balluff technical support
for further information.
The Safe I/O Module gets its IP address, IP mask
address and gateway address according information
stored in its Flash memory.
Note!
a,b,c designate any setting not
described as part of this table above
(e.g. the following positions: 000, [255 ..
399], [500 .. 998]).
Note!
In this mode, it is possible to store the
TCP/IP address information using an
EtherNet/IP commissioning tools (using
0xF5 TCP/IP Object).
Note!
If the module has never been
commissioned, the Safe I/O Module
starts in DCHP mode to obtain its first
IP address.