Setting name
9
Heating and cooling set point ranges
00
Heating set point upper limit
01
Heating set point lower limit
02
Cooling set point upper limit
03
Cooling set point lower limit
(b)
04
Overshoot setting
Automatic set back function
05
Set back operation
06
Set back operation start time
07
Set back operation stop time
08
Leaving water set back value
A
Quiet mode
00
Quiet mode type
01
Status
02
Not applicable. Do not change the default value.
03
Not applicable. Do not change the default value.
04
Not applicable. Do not change the default value.
b
Not applicable
00
Not applicable. Do not change the default value.
01
Not applicable. Do not change the default value.
02
Not applicable. Do not change the default value.
03
Not applicable. Do not change the default value.
04
Not applicable. Do not change the default value.
C
Setup on EKRP1HB digital I/O PCB
00
Solar priority mode setting
01
Alarm output logic
02
X1-X2 function: Bivalent operation status or
additional external backup heater
03
Bivalent ON temperature or additional external
backup heater temperature
04
Bivalent hysteresis or additional external backup
heater hysteresis
05
Not applicable.
d
Benefit kWh rate power supply/local shift value weather dependent
00
Switching off heaters
01
Unit connection to benefit kWh rate power supply
02
Not applicable. Do not change the default value.
03
Local shift value weather dependent
04
Not applicable.
05
Pump operation forced off or permitted during
backup heater is forced off at benefit kWh rate
power supply ([d-00]=0 or 1)
06
Not applicable.
E
Unit information readout
00
Software version
01
EEPROM version
02
Unit model identification. Do not change the default
value.
03
Liquid refrigerant temperature
04
Inlet water temperature
RKHBH/X016BB
Indoor unit for air to water heat pump system
4PW62576-1 – 10.2010
All manuals and user guides at all-guides.com
Installer setting at variance with default value
Date
Value
Default
Date
Value
value
Range
55
37~55
25
15~37
22
18~22
5
1
0 (OFF)
23:00
0:00~23:00
5:00
0:00~23:00
2
0
3
(c)
1
Read only
(c)
0
Read only
(c)
0
Read only
(c)
0
Read only
(c)
0
Read only
(c)
0
Read only
(c)
0
Read only
(c)
0
Read only
0
0
0
0
–25~25
3
0
0/1/2/3
0 (OFF)
0 (OFF)
0 (OFF)
0/1/2/3/4
0 (forced
off)
Read only
Read only
depending
on model
Read only
Read only
Step
Unit
1
°C
1
°C
1
°C
5~18
1
°C
1~4
1
°C
0/1
1
1:00
hour
1:00
hour
0~10
1
°C
0/2
0/1
1
0/1
1
0/1/2
1
1
°C
2~10
1
°C
1
0/1/2
1
1
0/1
1
1
°C
1
°C
Installation manual