How to check the existing piping settings
You can check whether the existing piping settings are enabled.
1. Check that the LED displays are placed in their initial status. If not, place them in the initial status.
2. Hold down SW01 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 9)
3. Press SW01 four times to set the LED displays (D800 to D805) to the "LED displays for existing piping settings"
shown below. If the setting is enabled, D802 lights and D804 and D805 flash rapidly. (Fig. 10)
4. Hold down SW01 and SW02 simultaneously for at least 5 seconds to return the LED displays to the initial status.
(Fig. 9)
LED displays indicated when step 3 is taken
D800
D801
D802
D803
D804
: ON,
: OFF,
: Slow flashing
When restoring the factory defaults
To restore the factory defaults in situations such as when relocating the units, follow the steps below.
1. Check that the LED displays are placed in their initial status. If not, place them in the initial status.
2. Hold down SW01 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 11)
3. Press SW01 14 times to set the LED displays (D800 to D805) to the "LED displays restored to factory defaults"
shown below. (Fig. 12)
(Fig. 11)
LED displays indicated when step 2 is taken
D800
D801
D802
D803
D804
: ON,
: OFF,
: Slow flashing
4. Hold down SW02 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 13)
5. Hold down SW01 and SW02 simultaneously for at least 5 seconds to return the LED displays to the initial status.
(Fig. 13)
LED displays indicated when step 4 is taken
D800
D801
D802
D803
D804
: ON,
: OFF,
: Slow flashing
39-EN
(Fig. 10)
LED displays for existing piping settings
D805
D800
D801
D802
D803
: ON,
: OFF,
: Rapid flashing
(Fig. 12)
LED displays restored to factory defaults
D805
D800
D801
D802
D803
: ON,
: OFF,
: Rapid flashing
D805
14

Troubleshooting

You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition
to using the check codes displayed on the wired remote controller of the indoor unit.
Use the LEDs and check codes for various checks. Details of the check codes displayed on the wired remote
controller of the indoor unit are described in the Installation Manual of the indoor unit.
LED displays and check codes
D804
D805
N
. o
1
Normal
2
Discharge temperature sensor (TD) error
3
Heat exchanger temperature sensor (TE) error
4
Heat exchanger temperature sensor (TL) error
5
Outside air temperature sensor (TO) error
6
Suction temperature sensor (TS) error
7
Heat sink temperature sensor (TH) error
8
Heat exchanger sensor (TE, TS) connection error
9
EEPROM error
10
Compressor breakdown
11
Compressor lock
D804
D805
12
Current detection circuit error
13
Case thermostat operation
14
Model data not set
15
Discharge temperature error
16
Power supply error
17
High pressure SW error
18
Heat sink overheating error
19
Gas leak detected
20
4-way valve reverse error
21
High pressure release operation
22
Fan system error
23
Drive device short-circuiting
24
Position detection circuit error
25
Compressor IPDU or other (not specifically identified)
: ON,
: OFF,
– 20 –
E
r r
r o
D800
: Rapid flashing (5 times/sec.)
* The LEDs and switches are located at the top right of
the P.C. board of the outdoor unit as shown in the
figure below.
D800
(Yellow) (Yellow) (Yellow) (Yellow) (Yellow) (Green)
Display
D801
D802
D803
D804
D805
EN
ID
LED displays
D801
D802
D803
D804
D805
ID
40-EN