AUX, power supply for weather station, for example. See "X10" for a description of connection of rain/wind
X7
sensors.
Data:
7.1 24V
7.2 0V
Maximum 500 mA
X9
Solid state output, for transmission of fault signal
Data:
9.1 Fault – Open contact = Fault, Closed contact = OK
9.2 Fault – Open contact = Fault, Closed contact = OK
Data
Max. voltage: 30 Vp (peak)
Max. current: 150 mA
Typical On-modstand: 15Ω
Max. On-resistance: 18 Ω
Max. switching speed: 2 ms
X10
Connecting wind / rain sensors of type WLA 330 or WLA 331.
Wind / rain sensor must be connected on both X10 and X7.
Data:
10.1 24V
10.2 Rain
10.3 GND / 0V
With the factory-set values the input is:
"Active" if resistor is less than 5kΩ
"Inactive" if resistor is greater than 8kΩ.
For values between 4 and 8Ω, the result will depend on the supply voltage.
Input has pull-up of approx. 1mA (min. 0.9mA, max. 1.1mA)
Connecting wind/rain and rain sensor
WLA 330 and WLA 331– the sensors settings are set on the sensor.
DIP switches 1-3 on WLA 330 must be set in relation to windspeed tolerances. See the guideline for WLA 330 for
DIP switch settings.
DS
DIP switch block with 8 DIP switches.
1
Maintained action
2
Rain delay
3
Extended hand timer
4
Surveillance
5
MotorLink®
6
100% speed
7
Accumulated step
8
Motor line 2, motors run independently
Factory setting = OFF
See chapter "DIP switch configuration" for detail information.