The locking actuators' power consumption is not included in the calculated 6A as the actuators and locking
actuators do not run simultaneously.
All actuators on the same motor line run/are operated at the same time.
All actuators on a motor line must be the same type.
Connection / cable diameter: flexible max 6 mm² / solid max 10 mm².
Cable length: see the chapter "Cable dimensioning".
Standard
actuators
±24V
Example with max. 3A current
consumption
a) 3 pcs. WMX 826-1
b) 2 sets of 3 pcs. WMX 504-3
c) 1 pc. WMU 883-1
d) 2 pcs. WMU 861-2
MotorLink
®
actuators
Examples with actuators per
motor line
Ex. 1: 4 pcs. WMX 823-1
Ex. 2: 2 pcs. WMX 836-2
Ex. 3: 3 pcs. WMU 826-3
Allowed actuator combinations on a MotorLink
The two motor lines on the CP card can each be connected to one of the below shown combinations.
-1 (single): one window with one single window
actuator. Up to four windows each with one
single window actuator can be connected
-2 (double): one window with two double
window actuators.
-3 (triple): one window with three triple window
actuators.
-4 (quad): one window with four quad window
actuators.
Connecting variants to standard actuators on motor line 1
®
motor line
10