WARNING
Make sure that the length of the refrigerant
pipe, the number of bends and the level
difference between the indoor unit and the
outdoor unit meet the requirements given in
the table.
CAUTION DANGER
– The Y joint must be installed horizontally.
An angle of more than 10° can cause
malfunctions.
– DO NOT install the connection pipe before
installing both the indoor and outdoor units.
– Insulate the gas side and liquid side pipes to
prevent water leaks.
Connection pipe sizes for the indoor unit.
Model
35M
Ø 9,52 mm (3/8")
70M
Ø 15.9 mm (5/8") Ø 9.52 mm (3/8")
105M
Ø 15.9 mm (5/8") Ø 9.52 mm (3/8")
Connection pipe sizes for the outdoor unit.
Based on the table below, select the diameters of the
connection pipes for the outdoor unit.
Main pipe dimensions (mm)
Model
Gas side
Ø 15,9 mm
70M
(5/8")
Ø 15.9 mm
105M-105T
(5/8")
Ø 15.9 mm
140T
(5/8")
Ø 15.9 mm
160T
(5/8")
28
Main pipe dimensions (mm)
Gas side
Liquid side
Ø 6,35 mm (1/4")
Liquid side
First Y joint
Ø 9,52 mm
FQZHN-01D
(3/8")
Ø 9.52 mm
FQZHN-01D
(3/8")
Ø 9.52 mm
FQZHN-01D
(3/8")
Ø 9.52 mm
FQZHN-01D
(3/8")
To use the Y joint, cut the pipe following the diagram in
"Fig. 34" to fit the internal and external pipe.
Liquid pipes
Gas pipes
10°
10°
Fig. 33
INDOOR UNIT CONFIGURATION
Set the switch
1 Master indoor unit: alternate 1 and 2 (one ON and the
other OFF)
2 Slave indoor unit: both 1 and 2 ON.
Installation
95 ±10
165 ±10
158 ±10
237 ±10
2
1
Fig. 34
Fig. 35

Werbung

Inhaltsverzeichnis
loading