8 Assemble the indoor unit on the suspension
bolts
using
suitable
Place the indoor unit level and check that it is aligned
with a spirit level to avoid any leaks.
Shock-proof shim
Washer
Suspension
bolt
WARNING
Ensure that the drain pipe slopes at least 1/100.
14
Fig. 11
locking
elements.
Nut
Protruding
part
Fig. 12
INSTALLATION OF ACCESSORY DUCTS
1 Install the filter (option) based on the size of the air
inlet.
2 Install the air passage frame between the body and
the duct.
3 The inlet and outlet air ducts must be sufficiently
spaced to avoid short circuits when the air passes
through.
4 Connect the duct following the diagram below:
Structure
fixing
Air
outlet
Insulation
Inspection
compartment
opening
5 For installation of the indoor unit, refer to the following
static pressure values.
Indoor unit
27M/35M
53M
70M
88M/105M
120M/140M/160M
6 Change the static pressure of the fan motor according
to the static pressure of the external duct.
WARNING
– Do not let the weight of the connection duct
rest on the indoor unit.
– When connecting the duct, use a non-
flammable flexible frame to prevent vibration.
– Wrap insulating foam material around the
duct to prevent condensate from forming.
On request of the end user, a liner can be
fitted in the duct to reduce noise.
Installation
Structure
fixing
Insulation
compartment
Air inlet
Dust filter
Fig. 13
Static pressure
(Pa)
0~60
0~100
0~160
0~160
0~160