9. Installation guidelines

Installation regulations
The respectively applicable local building, fire protection, and employer's liability insurance
association regulations shall always be complied with for the installation of mobile air heaters
(WLE) with closed combustion chamber.
Installation locations
The units shall not be operated at locations, where ignitable gas-air or dust-air mixtures can
occur (e.g. gas stations, paint shops, etc.).
Floors and ceilings shall be fire-retardant. Intake and outblow fittings shall not be narrowed.
Installation rooms
1. Installation of the WLE in closed, well ventilated rooms with chimney connection:
a. The minimum room size shall correspond to a mean heat requirement of the installation
room of 0.058 kW/m³.
b. The fresh air supply required to ensure proper combustion shall be ensured in any case
(windows, doors, or other openings).
Heat output
(kW)
25 kW
50 kW
80 kW
110 kW
140 kW
160 kW
2. Installation of the WLE in closed, well ventilated rooms without chimney connection:
a. The minimum room size shall correspond to a mean heat requirement of the installation
room of 0.058 KW/m³.
b. Natural air replacement of 2.5 times the room volume/h shall always be ensured
(removal of combustion gases and fresh air supply).
c. At least the following openings are required for this fresh air and exhaust air volume:
Fresh air:
2.8 m³
Exhaust air:
Heat output
(kW)
25 kW
50 kW
80 kW
110 kW
140 kW
160 kW
All manuals and user guides at all-guides.com
Room size
(m³)
500 m³
1000 m³
1400 m³
1900 m³
2500 m³
2800 m³
2.8 m³
Fresh air volume
(m³/h)
500 m³
1000 m³
1400 m³
1900 m³
2500 m³
2800 m³
41
Required fresh air
volume (m³/h)
50 m³/h
80 m³/h
130 m³/h
180 m³/h
220 m³/h
240 m³/h
Natural air replacement
(m³/h)
1250 m³/h
2500 m³/h
3500 m³/h
4750 m³/h
6250 m³/h
7000 m³/h
EN