System Commands - Balluff BTS M30E0-UUI-H0001-S04G Betriebsanleitung

Infrarot-temperatursensor
Vorschau ausblenden Andere Handbücher für BTS M30E0-UUI-H0001-S04G:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BTS M30E0-_ _ _-H0001-S04G
Infrared Temperature Sensor
15
IO-Link Interface
15.5

System Commands

Index
Data
Name
(dec)
Format
www.balluff.com
All manuals and user guides at all-guides.com
Access
Value Range (dec)
0x01 (1) = ParamUp-
loadStart
0x02 (2) = ParamUp-
loadEnd
0x03 (3) = Param-
DownloadStart
0x04 (4) = Param-
DownloadEnd
0x05 (5) = Param-
DownloadStore
0x06 (6) = ParamBreak
0x40 (64) = Teach
Apply
0x43 (67) = SP1 Two
Value Teach TP1
0x44 (68) = SP1 Two
Value Teach TP2
0x45 (69) = SP2 Two
Value Teach TP1
0x46 (70) = SP2 Two
Value Teach TP2
0x4F (79) = Teach
Cancel
0x4B (75) = Teach
Emissivity
0xA2 (162) = BDC
Reset
0xA5 (165) = Reset
Operating Hours
(Individual)
0x80 (128) = Device
Reset
0x82 (130) = Restore
Factory Settings
Remarks
Start Blockparameter Upload
Stop Blockparameter Upload
Start Blockparameter Download
Stop Blockparameter Download
Stop Blockparameter Download and
Upload Request
Abort block parameterizing
Save and apply switch points
Teach TP1 of SP1
Teach TP2 of SP1
Teach TP1 of SP2
Teach TP2 of SP2
Cancel teach-in
Teach emissivity (True Temperature
must first be set)
Reset BDC addressed by Teach-In
Channel to factory default
Reset individual operating hours
counter to 0
Reset device
Reset the sensor configuration to
the default factory settings
english
37