All manuals and user guides at all-guides.com
sary, personal safety equipment;
Evaluation of measuring results;
Selection of electrical installation material for safeguard-
ing shut-off conditions;
IP protection types;
Installation of electrical installation material;
Type of supply network (TN system, IT system, TT sys-
tem) and the resulting connecting conditions (classical
zero balancing, protective earthing, required additional
measures etc.).
Permitted cable cross sections for connecting to the wall
thermostat are:
For reasons of electrical safety, only the following
cables must be used for connecting to the Home-
matic IP Wired bus:
Telephone cable J-Y(ST)Y with 2 x 2 x 0.8
(= 0.5 mm²) or 4 x 2 x 0.8 (= 0.5 mm²),
shielded, TP
Ethernet installation cable S/FUTP, Type Cat5e or
higher with 2 x 2 x AWG22 (= 0.34 mm²) or
4 x 2 x AWG22 (= 0.34 mm²), shielded, TP
The shield (continuity wire) must be connected at
the bus connection of the Wired Access Point
(HmIPW-DRAP) to "–" (=GND). The shield may
not be connected to the wall thermostat.
54
Rigid cable: 0.12-0.50 mm