Verfügbare Sprachen

  • DEUTSCH, seite 1
3 609 929 A77/06.02 | SMdev
5 Commissioning
5.2
Jumper S1 bus power
detection
The SMdev interface module requires no
voltage from the DeviceNet to function
correctly. However, the voltage applied at
V+, V– is monitored. DeviceNet voltage
monitoring is switched on when the device is
delivered (Buspower detection = on, Fig. 2).
Figure 2: Jumper positions for Buspower detection
Jumper in on position: DeviceNet voltage
monitoring switched on.
Jumper in off position: DeviceNet voltage
monitoring switched off. This operation mode
is only to be used when connected to a
network without bus power supply.
Buspower detection
off
on
Bosch Rexroth AG
5.3

Display elements

LED (green/red)
MNS
Mod/Net status
Figure 3: Front view of SMdev interface module
LED display when power is supplied: The
following sequence checks if the interface
module is functioning properly:
– 0.25 seconds red,
– 0.25 seconds green.
Meanings of LED displays in operation:
LED display
Meaning
Off
After the device starts and while
checking for a duplicate MAC ID;
no voltage or no connection
within the network
Green
Network detected, connection to
master established, data is being
exchanged
Blinking green Network detected but connection
to master has not been
established; device is waiting for
the master to establish a
connection
Red
Error in the interface module,
critical connection error, device
has detected a network error
(duplicate MAC ID or bus off)
Blinking red
Error occurred while exchanging
data, connection monitoring time
elapsed, error can be reset
Blinking red/
Communication failed, serious
green
communication error