Enclosures D1h and D2h
Height [mm]
Enclosure
A
D1h
901
D2h
1107
UL fuses and conductor cross-sections to mains and motor, for installations in North America
Typical shaft
power P2
RK1/E1958/
J/E4273 T/
JFHR2
JDDZ
[kW (hp)]
1 x 200-240 V
1.1 (1.5)
KTN-R20
-
1.5 (2)
KTN-R30
-
2.2 (3)
KTN-R40
-
3 (4)
KTN-R40
-
3.7 (5)
KTN-R60
-
5.5 (7.5)
-
-
7.5 (10)
-
-
3 x 200-240 V
0.75 (1)
KTN-R10
JKS-10
1.1 (1.5)
KTN-R20
JKS-20
220
1)
1)
Width [mm]
a
B
b
844
325
180
1051
420
280
Bussmann
SIBA
RK1/
T/E4274 H/
Bussmann
JDDZ
E125085
JFHR2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
JJN-10
5017906-010
JJN-20
5017906-020
1)
Screw holes [mm]
Depth [mm]
∅d
C
c
378
20
378
20
Fuse type
Littel Fuse
RK1/SIBA
CC/Littel Fuse
E180276 RKI/
E71611 JFHR2
JDDZ
-
-
-
-
-
-
-
-
-
-
-
-
-
-
KTN-R10
ATM-R10
KTN-R20
ATM-R20
Weight [kg]
∅e
f
11
11
25
11
11
25
Maximum
conductor
Ferraz-Shawmut
cross-
section
RK1/E60314
JFHR2
[AWG]
-
10
-
7
-
7
-
7
-
7
-
7
-
2
A2K-10R
10
A2K-20R
10
62
125
1
2