DISPLAY VIEW: Main menu

Language
When power is first connected select language. From the factory it is preinstalled ENGLISH. You can choose
between: Danish, German, English, Spanish, French, Polish, Sloven, Italian. If you need to change
English
language later this can be done through the installers menu (service menu).
Water
If the power is switched on, this picture will be shown.
45°C
The picture shows the current Water temperature
Evapor
Evaporator temperature.
5°C
The picture shows the current evaporator temperature
Alarm
Alarm display.
Up to 3 alarms are shown. "0" = no alarm. Those Alarm types 1 to 10 are described in the alarm overview in
0 0 0
the following pages.
Those Alarms are reset through pressures of the button
Status
The current operating condition of the heat pump.
Off
The following announcements can occur:
"Off" = switched off, "Standby",
"H.Water " = works,
"Legionel" = 65°C Heating up in course,
"Def.Gas" – "Def.Air" - "Def.Stop"-
"Def.Stop" = Defrosting condition (see page 14), "alarm".
Setpoint
Shows the adjusted operating temperature.
45°C
The temperature can be changed through to pressures and again releasing the button, the operating
temperature will then flash. By turning the button, the desired water temperature will occur. If the desired
water temperature is reached, the button is pressed again for receipt. The normal operating temperature is
between "45°C" and "55°C".
T min
Minimum temperature.
35°C
The temperature can be changed through to pressures and again releasing the button, the operating
temperature will then flash. By turning the button, the desired minimum water temperature will occur. If the
desired temperature is reached, the button is pressed again for receipt. The minimum temperature is
normally about. "35°C".
If the water temperature become lower than "T min" , the additional heating system will be activated, if
you in the menu "Heatpump" have selected, e.g. "HP+EL" (or HP+Boil if boiler is installed)
Same function as T min but are used for "drawdown function" and "holiday function" The factory setting
T2 min
10°C
is "10°C".
Heat
Here you can select the combination of the Heat source.
pump
There are the following options in the program:
"OUT", "HP", "EL", "HP+EL","BOILER", "HP+BOIL".
HP+EL
If no boiler is installed, the last 2 combinations are not to be used
Legionel
Here can the automatic Legionellafunction be switched on.
Off
If switched ("ON") the heatpump will once weekly increase the temperature to 65°C, in order to kill
possible bacteria
FanCon
Fan enterprise, when the heat pump is in standby.
When selected "Off" the fan will stop together with the heat pump.
Off
When selected "Low" for low or "High" for high speed in the condition standby.
(= constant ventilation)
FanOper
Fan speed, when the heat pump runs.
"Low" = low speed
High
"High" = high speed
Temp 1
Here can additional sensor for f. ex. boiler water or outside temperature to be installed.
---°C
Temperature range -40°C to 100°C. Only available if signal anode installed.
Solarcel
Solar cells are connected to the system, to use for external operating mode.
"Off" = Solar cells are not connected to system or not chosen to be used by the user.
Off
"On" = Solar cells run as external operating mode.
See "page 10 electrical diagram for connection to controller
SC-HP
5°C – T max
52°C
With solar cells selected, control the hot water production temperature by using only heat pump.
SC-EL
5°C – T max
53°C
With solar cells selected, control the hot water production temperature by using only supplementary heating.
Holiday
"Off", "1 week", " 2 weeks", "3 weeks", "3 days", "Manual"
Choose which holiday function to use and the water temperature lowers to "T2 min".
Off
Man.days
1-99
Define manually how many days on holiday. Water temperature lowers to "T2 min"
1
13