Vereinfachte Liste der Modbus-Netzwerkvariablen
Die vereinfachte Liste Modbus enthält die am häufigsten verwendeten Daten für die Überwachungskommunika-
tion in Modbus. Alle diese Datenpunkte können über den Corrigo Controller ausgelesen werden. Die verfügba-
ren Informationen hängen von der Konfiguration der Anlage ab. (Betriebsart oder gewählte Optionen, Montage /
Verkabelung usw.)
Function
Address Read/Write
40428
Set point supply
air flow
40429
Pressure set
point on supply
40024
air
40030
Set point exhaust
air flow
40031
Pressure set
point on exhaust
40449
air
Speed selector
40368
30032
Supply air flow
30015
Supply air
30013
pressure
30033
Exhaust air flow
30016
Exhauster
30014
pressure
Boost
10008
Supply air
30007
temperature
Exhaust air
30009
temperature
Outdoor air
30001
temperature
Water coil
30019
temperature
Total alarms
10184
DEUTSCH
FANS CONTROL
Setpoint supply air flow ,Normal Speed ,CAV (Constant Air
R/W
Volume) running mode
Setpoint supply air flow ,Reduce Speed ,(Constant Air Volume)
R/W
running mode
Pressure set point in COP (COnstant Pressure) running mode,
when pressure transmitter is installed on the supply air duct.
R/W
Value: 0 .. 9999 means 0 .. 999.9Pa
Setpoint exhaust air flow ,Normal Speed ,CAV (Constant Air
Volume) running mode
R/W
Setpoint exhaust air flow ,Reduce Speed ,(Constant Air Volume)
running mode
Pressure set point in COP (COnstant Pressure) running mode,
when pressure transmitter is installed on the exhaust air duct.
R/W
Value: 0 .. 9999 means 0 .. 999.9Pa
Manual speed selection
R/W
0=stop, 1=Reduce speed , 2=Normal speed, 3=Automatic
(according to timer program)
READING AIR FLOW /PRESSURE
In COP mode with pressure transmitter on supply air duct =
Value of ∆Pa mesurement on supply air fan nozzle
Air flow is obtain by calculationl: Air flow= K*√ ∆P
R
Coef.K value corresponding to the unit; √∆P= √read value/10
Value: 0 .. 9999 signifiant 0 .. 999.9Pa
Supply air flow (M3/h), in CAV, VAV ou COP on exhaust air
R
running mode
Pressure on supply air fan (Pa), in COP on supply air duct
R
Value: 0 .. 9999 means 0 .. 999.9Pa
In COP mode with pressure transmitter on exhaust air duct =
Value of ∆Pa mesurement on supply air fan nozzle
Air flow is obtain by calculationl: Air flow= K*√ ∆P
R
Coef.K value corresponding to the unit; √∆P= √read value/10
Value: 0 .. 9999 signifiant 0 .. 999.9Pa
Exhaust air flow (M3/h), in CAV, VAV ou COP on exhaust air
R
running mode
Pressure on exhaust air fan (Pa), in COP on supply air duct
R
Value: 0 .. 9999 means 0 .. 999.9Pa
Status of boost function
R
0=boost off; 1=boost on
TEMPERATURE STATUS
Read the supply air temperature
R
Value: -990 .. +990 means -99.0 .. +99.0 °C.
read the exhaust air temperature
R
Value: -990 .. +990 means -99.0 .. +99.0 °C.
Read the outdoor air temperature
R
Valeurs: -990 .. +990 signifiant -99.0 .. +99.0 °C.
Read the water coil temperature (anti frost probe value)
R
Valeurs: -990 .. +990 signifiant -99.0 .. +99.0 °C.
ALARMS
A or B Alarm status
R
0=Normal, 1=Alarm
Description
82/100
Accepted value
0..max air flow of the
unit
0..max air flow of the
unit
0..max available
pressure
0..max air flow of the
unit
0..max air flow of the
unit
0..max available
pressure
0, 1, 2 ou 3
0..max flow
0..max flow
0..max value of the
unit
0..max value of the
unit
0..max value of the
unit
0..max value of the
unit
0 or 1
-999..999
-999..999
-999..999
-999..999
0 or 1