• Projection margin in flaring : B (Unit : mm)
Rigid (Clutch type)
Outer diam. of
copper pipe
6.4
9.5
12.7
15.9
Imperial (Wing nut type)
Outer diam. of copper pipe
Connection of refrigerant pipe
Connect all the refrigerant pipes with flare connecting
work.
• Since the atmospheric pressure only is sealed as the
sealing gas, it is not abnormal that "Pushu..." sound
is not heard when the flare nut is removed.
• Be sure to use a double spanner for pipe connecting
work of the indoor unit.
• Refer to the following table for tightening torque.
Connecting pipe
outer dia. (mm)
Ø6.4
Ø9.5
Ø12.7
Ø15.9
Downloaded from
www.Manualslib.com
R410A tool used
Conventional tool used
R410A
R22
R410A
0 to 0.5 (Same as left)
1.0 to 1.5
0 to 0.5 (Same as left)
1.0 to 1.5
0 to 0.5 (Same as left)
1.0 to 1.5
0 to 0.5 (Same as left)
1.0 to 1.5
R410A
6.4
1.5 to 2.0
9.5
1.5 to 2.0
12.7
2.0 to 2.5
15.9
2.0 to 2.5
Work using double spanner
Tightening torque
Re-tightening
(N•m)
torque (N•m)
14 to 18
(1.4 to 1.8 kgf•m)
33 to 42
(3.3 to 4.2 kgf•m)
50 to 62
(5.0 to 6.2 kgf•m)
68 to 82
(6.8 to 8.2 kgf•m)
manuals search engine
Airtight test/Air purge, etc.
For airtight test, air purge, addition of refrigerant, and
gas leak check, follow the Installation Manual attached
to the outdoor unit.
R22
0.5 to 1.0
Open fully valves of the outdoor unit
0.5 to 1.0
0.5 to 1.0
Gas leak check
0.5 to 1.0
Check with a leak detector or soap water whether gas
leaks or not, from the pipe connecting section or cap
of the valve.
R22
1.0 to 1.5
Use a leak detector manufactured exclusively for
1.0 to 1.5
HFC refrigerant (R410A, R134a, etc.).
1.5 to 2.0
1.5 to 2.0
Heat insulating process
Perform heat insulating for pipes at liquid side and gas
side separately.
In cooling time, temperature at both liquid and gas
sides becomes lower.
Therefore, perform heat insulating process sufficiently
to avoid dewing.
• For heat insulator of pipe at gas side, be sure to use
one with heat-resisting temp.120°C or more.
• Using the attached heat insulating pipe, perform heat
insulating process securely for pipe connecting part
of the indoor units without clearance.
Apply the thermal insulation to the pipe connecting
section of the indoor unit securely up to the root
without exposure of the pipe. (The pipe exposed to
the outside causes water leak.)
18
(1.8 kgf•m)
Indoor unit
42
(4.2 kgf•m)
50
(5.0 kgf•m)
68
(6.8 kgf•m)
8
REQUIREMENT
REQUIREMENT
Pipe side
(Required at the site)
Attached heat insulating pipe