The condensate drain can be identified from the plate affixed directly inside the machine
The connection pipes must be suitably supported so that they do not weigh down on the
machine.
2.5

ELECTRICAL CONNECTIONS

The electrical connections of the machine must be defined during the system design.
DANGER
The electrical connections must only be designed and
completed by personnel with precise technical competence or
skills in the field of activity.
Before proceeding, personnel must disconnect all power supply
sources, making sure that no one may inadvertently re-connect
them.
The characteristics of the power supply network must comply with the IEC 60204-1
standards and the local standards in force and be adequate for the absorption
requirements shown in the wiring diagram.
The machine must be connected to single-phase power supply and to TN(S) type three-
phase power supply.
Refer to local bylaws. Only power the system if the cooling / water (humidifier) circuit is
charged.
OBLIGATION
The electric power supply line must include a general circuit
breaker for the disconnection of the machine from the power
source.
In accordance with the IEC 60204-1 standard, the handle of the circuit breaker must be
easy to access and at a height between 0.6 and 1.9 metres from the floor. The power
supply must never be excluded, except during maintenance.
UM_MULTIDENSITY_00_Z_09_20_ML
2.5.1
Use a multipole conductor with protective sheath. The cable section depends on the
maximum absorbed current of the machine (A) as shown in the dedicated wiring diagram.
For the entry of the power cables in the machine use the holes provided at the base by the
Manufacturer.
Fix the cables to the internal machine riser using cable ties. Do not touch hot or sharp
surfaces.
The power cable must not be placed into the machine cable ducts.
m-MRAC
MODEL
POWER SUPPLY
STANDARD UNIT
Max power input (FLI)
Max current input (FLA)
2.5.2
The control circuit is shunted off the power circuit from inside the switchboard.
A
Every unit is equipped with:
1)
2)
3)
4)
1
Both on the backdoor terminal block and on the CNEF-24 connector, the following
connections and signals are available:
The sliding electrical panel also comprehends a ModBus/IF card for the installer to connect
to, in order to set the M-NET addresses.
Where the rotational Dip-Switcher can be setted:
*1 first digit of address (tens)
*2 second digit of address (units)
*3 assign each indoor unit a number from 1 to 10 (each unit must have its own address)
The only DipSwitches to be set in the electrical panel are for the M-Net addresses on the
ModBus/IF card.
23

MACHINE POWER SUPPLY

009
230/1/50-60
kW
0,36
A
3,0

AUXILIARY ELECTRICAL CONNECTIONS

a sliding electrical panel
a CNEF-24 connector on the top of the unit for communication and control
a C14 connection for the power supply
an additional terminal block accessible from the backdoor
M-Net (mandatory)
P-Lab (mandatory)
ModBus (optional)
Remote On-Off (optional)
Alarm A (optional and configurable)
Alarm B (optional and configurable)
Flooding sensor (if present)
Fire-smoke detector (if present)
Power supply for the fire-smoke detector (optional)
SW
SW1 01
SW1 02
SW1 03
SW1 06
English
015
025
230/1/50-60
230/1/50-60
0,70
0,93
5,9
7,4
2
ModBus/IF card
with screwed
metal cover
Settings
*1, *3
*2, *3
-1
OFF
-2
OFF
-3
OFF
-4
OFF
0N
ORIGINAL INSTRUCTIONS