Herunterladen Inhalt Inhalt Diese Seite drucken

Power Consumption - Desoutter CVI3 Schnellstartanleitung

Vorschau ausblenden Andere Handbücher für CVI3:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 36
6159932290_13
Line protection
- Each controller includes a GFCI (Ground
Fault protection) and 16 A over current
protection (integrated to the GFCI).
- No fuse.
Differential circuit breaker
Voltage
Max. current
Curve
Differential sensitivity
For information:
- standby consumption is 17 W.
- the max power available supplied via the
24V power supply (between pin 2 and 3 on
I/O connector):
CVI3 Essential, CVI3 Vision or CVI3
Function: 1 A (24V)
TWINCVI3: 2 A (24V).

Power consumption

The apparent power consumption is the only
needed information.
S = apparent power measured in Volt-Amps (VA)
S = U
x I
rms
rms
The apparent power peak is 6 kVA.
The duration of the peak is < 0.5 s.
CVI3 Essential / CVI3 Function / CVI3 Vision
The mean apparent power is always ≤ 1 kVA.
Single Phase 200-240 V
Single Phase 100-120 V
TWINCVI3
The mean apparent power is always ≤ 2 kVA.
Single Phase 200-240 V
Single Phase 100-120 V
External power consumption
The decision to install an external differential
circuit-breaker depends on the type of internal
electric network in the customer's plant.
This device detects any insulation defect
between one of the phases of the network and
the earth, immediately stops the tool by automatic
power cutoff and protects the operator from any
electric shock.
200-240 V
16 A
D
30 mA
I
≤ 4.35 A
rms
I
≤ 8.7 A
rms
I
≤ 8.7 A
rms
I
≤ 17.4 A
rms
Should circuit-breakers be installed at the line
head, we recommend that you select equipment
with the following specifications:
- Single-phased 240V 16A - curve D
- Single-phased 110V 32A - curve D.
Controller power consumption: current inlet
Apparent power (S)
measured in VA
Impedance
phase angle
True power (P)
measured in Watts
P = true power measured in units of Watts
T
1
u(t) x i(t)dt
P
T
0
where T is the period of the signal
In a CVI3 controller, the power peak is 5kW.
To dimension an installation, the apparent power
consumption is the only needed information.
S = apparent power
S
U
x I
rms
measured in Volt-Amps (VA)
The apparent power peak is 6kVA the duration of
the peak is < 0.5 s
The mean apparent power is always ≤ 1 kVA.
SINGLE PHASE 230 V
At 230 V
I
x
230
rms
1000
I
rms
230 A
I
≤ 4.35 A
rms
Then we recommend to use a circuit breaker 10A
Curve D.
22 / 144
The "Power triangle"
Reactive power (Q)
measured in VAR
rms
≤ 1 kVA
English
06/2020

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Cvi3 essentialCvi3 functionCvi3 visionTwincvi3Cvi3 function estopCvi3 vision estop ... Alle anzeigen

Inhaltsverzeichnis