15.
Eingänge
15.1. PT1000-Temperaturfühler
Die Verbindungskabel zu den Temperaturfühlern bewirken einen ohmischen Widerstand, der den Messwert des
entsprechenden Fühlers erhöht, durch diesen Korrekturwert kann der Fehler kompensiert werden.
Fühlertyp:
Fühlerleitung:
Tiefpassfilter:
5
0.1 0.4°C 0.9°C 1.3°C 1.8°C 2.6°C 3.5°C 4.4°C 5.3°C 7.0°C 8.8°C 10.5°C 13.1°C
0.2 0.2°C 0.4°C 0.7°C 0.9°C 1.3°C 1.8°C 2.2°C 2.6°C 3.5°C 4.4°C
0.3 0.1°C 0.3°C 0.4°C 0.6°C 0.9°C 1.2°C 1.5°C 1.8°C 2.3°C 2.9°C
0.4 0.1°C 0.2°C 0.3°C 0.4°C 0.7°C 0.9°C 1.1°C 1.3°C 1.8°C 2.2°C
0.5 0.1°C 0.2°C 0.3°C 0.4°C 0.5°C 0.7°C 0.9°C 1.1°C 1.4°C 1.8°C
0.6 0.1°C 0.1°C 0.2°C 0.3°C 0.4°C 0.6°C 0.7°C 0.9°C 1.2°C 1.5°C
0.7 0.1°C 0.1°C 0.2°C 0.3°C 0.4°C 0.5°C 0.6°C 0.8°C 1.0°C 1.3°C
0.8 0.1°C 0.1°C 0.2°C 0.2°C 0.3°C 0.4°C 0.5°C 0.7°C 0.9°C 1.1°C
0.9 0.0°C 0.1°C 0.1°C 0.2°C 0.3°C 0.4°C 0.5°C 0.6°C 0.8°C 1.0°C
1 0.0°C 0.1°C 0.1°C 0.2°C 0.3°C 0.4°C 0.4°C 0.5°C 0.7°C 0.9°C
1.5 0.0°C 0.1°C 0.1°C 0.1°C 0.2°C 0.2°C 0.3°C 0.4°C 0.5°C 0.6°C
Korrektur notwendig unter
→ Menü → Betriebs-Einstellungen → Eingänge → Korrek tur Temp.-Eingänge
Leitungslänge in Metern
10
15
20
WPC3 Service-Handbuch Version 1.26, 08.03.2012
PT1000
Kupfer-Zweidrahtleitungen, geschirmt ab 5m Länge und
bei Parallelverlegung zu Netzleitungen
Ein einstellbares Tiefpassfilter, reduziert Störungen im
messbaren Bereich. Das Messsignal wird jedoch in
Abhängigkeit der Grenzfrequenz verzögert dargestellt. Je
höher die Grenzfrequenz desto kleiner die Verzögerung.
30
40
50
60
80
100
5.3°C
3.5°C
2.6°C
2.1°C
1.8°C
1.5°C
1.3°C
1.2°C
1.1°C
0.7°C
120
150
6.6°C
4.4°C
3.3°C
2.6°C
2.2°C
1.9°C
1.6°C
1.5°C
1.3°C
0.9°C
Seite 86/110