Vertical roof terminal, type C31

Dimensions of flue pipe:
The fireplace is supplied with an outlet spigot Ø100/Ø150 mm or Ø130/Ø200 mm, depending on the
model. This flue dimension can be used for the entire flue. Alternatively, a Ø130/Ø200 adapter can be
fitted, so that this flue dimension can be used for the rest of the flue.
Flue terminal:
Ø130/Ø200 Item no. USDVC 130
Ø100/Ø150 Item no. USDVC 100
Minimum vertical length of flue pipe 0.5 m.
Restrictor plate in flue, Ø100/150 and Ø130/200
Fit the flue gas restrictor for Ø100/Ø150 together with the interior flue gas spigot!
Vertical height < 1 m: No restrictor
Vertical height < 1–2 m: Ø62 mm restrictor
Vertical height > 2 m: Ø76 mm restrictor
NB:
Examples of flue solutions are shown at the back of the manual under the section 'Examples of
flue solutions'.

Pipework

When you start installing the pipework for the gas fireplace, it is im-
portant that the flue pipe faces the correct way. The end must only
have a single "ring" facing down in the gas fireplace. See image.
VERTICAL ROOF TERMINAL, TYPE C31
GB - 31