Horizontal Wall Terminal, Type C11 - RAIS/attika NEXO 100 GAS Installationsanleitung

Gaskamin
Inhaltsverzeichnis

Werbung

Horizontal wall terminal, type C11

Dimensions of flue pipe:
The fireplace is supplied with an outlet spigot, dimension Ø100/Ø150 mm. This flue dimension can be
used for the entire flue. Alternatively, a Ø130/Ø200 adapter can be fitted, so that this flue dimension
can be used for the rest of the flue.
Flue terminal:
Ø130/Ø200 Item no. USDHC 130
Ø100/Ø150 Item no. USDHC 100
Maximum length of flue pipe to outer wall (H)
= 4 X vertical flue pipe length (V) -1 for Ø130 / Ø200 pipe.
= 2 X vertical flue pipe length (V) for Ø100 / Ø150 pipe.
Maximum permitted length (V + H) = 15 m.
Minimum vertical height of flue pipe = 0.5 m.
Vertical length
of flue pipe (V) in
metres
0 .5
1
1 .5
2
2 .5
3
3 .5
4
4 .5
5
5 .5
6 .5
7
7 .5 <
Flue gas restrictor for Ø100/Ø150
Vertical height < 1 m: No restrictor
Vertical height < 1–2 m: Ø62 mm restrictor
Vertical height > 2 m: Ø76 mm restrictor
30 - GB
HORIZONTAL WALL TERMINAL, TYPE C11
Maximum length
Maximum length
of horizontal flue
of horizontal flue
pipe (H) in metres
pipe (H) in metres
Ø130/Ø200
Ø100/Ø150
1
1
3
2
5
3
7
4
9
5
11
6
13
7
15
8
15
9
15
10
15
11
15
13
15
14
15
15