BES Q08ZC-YPL20B-BP00,3-GS_ _
Inductive Sensors
5
IO-Link Functions (continued)
5.2
Teach Instructions (Single Value Teach in
Single Point Mode)
The Single Value Teach in Single Point Mode is
explained using switch point 1 (SP1).
For the Single Value Teach in Single Point Mode applied
here, both setpoints are taught in at the same time.
Setpoint 2 is calculated with the hysteresis defined by
Index 0x003D Subindex 0x03 and SP1.
Requirements
The sensor is installed, aligned and in IO-Link mode.
Teach-in
1. Position the object within the measuring range.
2. Teach in the teach point: Send system command 0x41
to the sensor.
Access
Index
Value
W
0x0002
0x41
3. Verify whether SP1 has been taught in successfully:
Read out and check the Teach-In-Status parameter
using index 0x003B.
Access
Index
Value
R
0x003B
0x01
0x07
⇒ SP1 and SP2 are successfully taught.
www.balluff.com
Meaning
SP1 Single Value Teach
Meaning
SP1successfully Applied Teach-in
State = SP1 SUCCESS (0x01)
Teach-in State 0 ERROR
Result
Teach-in ended successfully
Return to step 2
english