Sensor Wiring

515 (8510), 525,
2000, 2100, 2507,
2536 (8512), 2540
2537
Blk Red Shld
S1
2551*
Black
Red
White
Shield
Connect the silver (shield) wire
to earth ground in case of EMI
noise interference.
2552
Black
Brown
White
Blue
Shield
Black
Red
Shield
-
+
S2
Black
Red
White
*2551 Blind Magmeter
Output Selection Jumpers
S
L
3
Black
Brown
White
X
Blue
Shield
Frequency
4
3
3
S L
4
3
Frequency
No
connection
9900-1BC Batch Controller Manual
2551 Technical Notes:
• When the blue jumper
illustrated is placed
over both pins, the
2551-XX-11
(Blind Magmeter)
outputs an open
collector frequency
signal. When the
jumper is removed
(or placed over one pin
for storage) the
2551-XX-11 outputs a
Digital (S
L) signal.
3
2551 & 2552
Technical Notes:
• Either Frequency or
Digital (S
L) may
3
be used.
• The frequency output
will be displayed as
positive fl ow regardless
of the fl ow direction.
• Signet recommends
confi guring the 2551
with the Digital (S
output because it is
more accurate.
• Input sensor type
is selected by
choosing between
"SENSOR FREQ" and
"SENSOR S3L" in the
INPUT menu.
• 5 VDC power is
provided to the
2551 Magmeter by
the 9900-1BC.
No additional power
is required.
L)