This is the normal display
(when batch is running).
VIEW Mode Menu - Batch Running
16
9900-1BC Batch Controller Manual
Stop Running Batch Press ENTER to stop batch that is running.
Note: ENTER button stops batch in any screen on VIEW Mode.
Time Left displays estimated time remaining (in minutes) until batch
is completed.
Percent Complete displays percent remaining or percent completed of
running batch. Count direction based on COUNT UP/DOWN setting in
INPUT menu.
Flow Rate displays current fl ow rate of running batch.
Output Current displays the output loop current in milliamperes (mA).
Source Volume displays the calculated remaining source volume.
Shown if SOURCE VOLUME is ON.
Relay Status displays relay status for Relays 1, 2 and 3. One of three
states (OFF, ON, PLS) for each relay will be displayed.
BATCH Setup Checklist
1. Set the Units of Measure in Input Menu.
2. Set Flow Timebase in Input Menu.
3. Set Sensor Type (Freq or S
Menu.
4. Set Batch Size in Input Menu.
5. Set K-Factor (pulses per Unit Volume)
from Flow Sensor manual in CAL Menu.
6. Set up relay functions and other settings
for your own application.
L) in Input