GF Signet 9900-1BC Produktanleitung Seite 17

Batch controller system
Vorschau ausblenden Andere Handbücher für Signet 9900-1BC:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

VIEW Mode Menu - Batch Stopped
Start Batch Press Up or Down arrows to select the desired batch number.
Press ENTER to start selected batch. Selected batch alternately displays on the
bottom line of the display.
(Confi rmation screen or password screen are user-selectable in INPUT menu.)
Available batches determined by the number of stored batches whose size is not zero.
Resume/Cancel Batch Displays when a batch is stopped without completing. Press
the ► key to select either RESUME or CANCEL and then press ENTER to either
resume the batch or cancel it. A confi rmation or password screen for resuming a
batch is user selectable. This screen will not display if the batch reaches completion.
Override Batch In Simple mode the user can temporarily change the size of the
batch. The batch returns to the programmed value at the end of the current batch
run. In Advanced mode the Override can be set to permanently change the size of
the batch value. A batch is overridden by pressing the ► to edit the batch size.
Manual Batch is used for "topping off" a batch, after the batch has completed. The
Batch Controller will open the valve as long as the user simultaneously holds down
the ▼ and ► keys.
Source Volume shows the calculated remaining source volume.
Displays if SOURCE VOLUME is ON. Reset source volume with ► key.
Note: If PWD REQUIRED is set to YES, you may be prompted to enter your
password. PWD REQUIRED setting can be changed in the OPTIONS menu.
Reset Volume? Confi rmation screen for resetting SOURCE VOLUME.
Press ▲ or ▼ to select YES and press ENTER to reset source volume.
Resettable Totalizer displays the resettable totalizer. Press ► to reset the
totalizer. Note: If PWD REQUIRED is set to YES, you may be prompted to enter
your password. PWD REQUIRED setting can be changed in the OPTIONS menu.
Reset Total? Confi rmation screen for clearing the resettable Totalizer.
Press ▲ or ▼ to select YES and press ENTER.
Permanent Totalizer displays the Permanent Totalizer value
(note the "P" indicating Permanent). Pressing ► displays units of measure.
Overrun displays the amount of overrun volume detected after the 9900-1BC
deactivates the batch relay, triggering valve closure. Overrun resets each time a
new batch starts.
Batch Count shows the number of batches which have run to at least 90% of
completion. Press ► to reset Batch Count.
Note: If PWD REQUIRED is set to YES, you may be prompted to enter your
password. PWD REQUIRED setting can be changed in the OPTIONS menu.
Reset Count? Confi rmation screen for clearing the Batch Count.
Press ▲ or ▼ to select YES and press ENTER.
Customizable Label is the View name assigned to the 9900.
Default is BATCH for 9900-1BC.
9900-1BC Batch Controller Manual
17