Batch controller system
Vorschau ausblenden Andere Handbücher für Signet 9900-1BC:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

RELAY Menu
RELAY MULTIPLE Mode options (see discussion on page 12)
RELAY TWO STAGE Mode option (see discussion on page 12)
Missing Signal On/Off Energizes selected relay if signal is missing.
Select ON or OFF.
Overrun On/Off Energizes selected relay if overrun occurs. Select ON or OFF.
Hi Flow On/Off Energizes selected relay if Hi Flow condition occurs. Select ON or OFF.
Error On/Off Energizes selected relay if an error condition occurs. Select ON or OFF.
Main Relay Select (ADVANCED Mode only) Selects the specifi ed relay as the
main relay for two-stage valve control. This relay will be de-energized when the
batch volume reaches the setpoint percentage.
Setpoint Percent Select Selects the percentage of batch volume at which the
main relay will be de-energized. Default = 95.0%.
Bypass Relay Select Selects the specifi ed relay as the Bypass relay for two-stage
valve control. This relay will remain energized while the batch is running.
Relay Bypassed The specifi ed relay is in Bypass.
Note: A relay is taken out of bypass using the Bypass select screen, found under
the relay which is in TWO STG Mode.
9900-1BC Batch Controller Manual
21