Relay Mode Settings
HI FLOW – High Flow:
In HI FLOW Mode, Relay is energized at
Set Flow value and will be de-energized
at Set Flow value minus Hysteresis value.
If STOP BATCH is set to YES, the
hysteresis is ignored. A batch stopped for
a high fl ow condition will not automatically
resume when the fl ow decreases below
the hysteresis level. User interaction is
required to resume the batch.
EOB PULS – End of Batch Pulse:
Generates a pulse at the end of a batch
which can be used for external counter or
to start a second batch controller.
OVERRUN – Overrun:
Activates relay when Overrun reaches
the specifi ed volume (see Set Overrun
Volume, pg. 19).
Note: The Overrun Alarm Volume must be
greater than the Manual Compensation
Volume. If the Overrun Alarm Volume
is less than or equal to the Manual
Compensation Volume, the Overrun
Alarm will activate on every batch.
SRC VOL – Source Volume:
Activates relay when Source Volume falls
to specifi ed volume ( only available when
"Source Volume" is ON ).
Advanced Mode
(See Input Menu - Page 17)
Process
High
Setpoint
Hysteresis
Relay energized
Relay de-energized
0%
Relay energized
Relay de-energized
% Batch Percentage
0%
100%
Relay energized
Relay de-energized
% Batch Percentage
Relay energized
Relay de-energized
9900-1BC Batch Controller Manual
Time
100%
Time
Overrun
Time
11