2 - CONFIGURING THE CONTROLLER
The controller and display must be configured before the unit is commissioned.
2.1 - Configuring with Single-Phase EC Boxes:
The value of the display's factory-set address is '32'. It is pointless to only change it in the Single-Phase EC Box configuration.
If the nn field is set to '0', the terminal will use the Point-to-Point Protocol (not the pLAN) to communicate with the controller and the
"I/O Board address: xx" field will disappear as it will not be necessary.
It is however essential to assign a controller to the pLDPRO display by giving it an address (I/O Board address):
■ Power up the Single-Phase EC Box
■ Switch to configuration mode, by simultaneously pressing the , and
will be displayed, with the cursor flashing in the top left corner:
■ To change the controller address (I/O Board address) press twice: the cursor will move to the (--) field.
■ using the key, select the value 01, and confirm by pressing the
previously, the page for the following figure is displayed and the new value will be stored in the terminal's permanent memory.
■ Press
again.
■ Set Trm1 to 32 by pressing , press .
■ Set value 'Pr' (Private) to 'Sh' (Shared) by pressing , press .
■ Go to 'No' by pressing several times, select 'Yes' by pressing then .
The controller now has the correct address.
28
XX7515390-03_CONTROL_11_2019_BOX_MONO_EC_42AM.indb 28
XX7515390-03_CONTROL_11_2019_BOX_MONO_EC_42AM.indb 28
keys for approx. 5 seconds; the page shown below
Display address
Setting ................ : 32
I/O Board address
: --
key again.If the value selected is different from that stored
Terminal config
Press Enter
To continue
P:01 Adr Priv/Shared
Trm1
32 Pr
Trm2
None
--
Trm3
None
-- Ok?No
P:01 Adr Priv/Shared
Trm1
32 Sh
Trm2
None
--
Trm3
None
-- Ok?No