Controller Information - Carrier WTC-B-207 Installationsanweisungen

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 32

2. Controller information

Power
Voltage
100-240 VAC; ±15%; 50/60 Hz
Typical
0.9 W plus all external loads
Consumption
(external loads must include
the power consumption of
any connected module)
Double Insulation Device
Overvoltage Category II - 2.5 kV
LonTalk Interoperability
Communication
LonTalk protocol;
LonMark certified
Channel
TP/FT-10; 78 Kbps
LonMark Interop.
Version 3.4
Guidelines
Device class
SCC Fan Coil
LonMark Functional Profile
- Node Objects
Node Object #0000
- SCC Object
SCC Fan Coil #8501
- Lamp Objects
Lamp Actuator #3040
- Sunblind Objects
Sunblind Actuator #6110
Connection
2 wires: LON1 / LON2
BACnet MS/TP Interoperability
Communication
BACnet MS/TP; BTL certified
BACnet Profile
B-ASC
EOL Resistor
Built-in, dip switch selectable
Baud Rates
9600, 19 200, 38 400, 76 800 bps
Addressing
Dip Switch
Connection
3 wires: Net+ / Net- & COM
Environmental
Operating
Temperature
Storage Temperature
Relative Humidity
Altitude
Pollution Degree
Enclosure - control box
Material
ABS type PA-765A POLYLAC
Dimensions 272 x 190 x 88 mm OR
395 x 195 x 65 mm (42GW only)
IP
30 when equipped with strain
relief and terminal block cover
+5°C to +40°C
-20°C to +70°C
+20 to 90%
non-condensing
< 2000 m
2
Subnetwork
Communication
RS-485
Cable
Cat 5e, 8 conductor twisted pair
Connector
RJ-45
Topology
Daisy-chain configuration
Inputs
Measurement Category: CAT I
Universal Inputs
Software configurable
(UI1, UI2)
- Voltage
0-10 VDC
- Temperature
10 kΩ Type II, III; 10 kΩ at 25°C;
sensor
Accuracy: ± 0.1°C at 25°C
Digital Inputs
Software configurable;
207: X9-DI1
Dry Contact 0-3.3 VDC
307: X9-DI1,-DI2
Power Supply
5 VDC for polarization
Output (V ref)
I < 1 mA
Outputs
Triac Outputs
PWM (Typically Thermal Valve
207: X5-CV,
Control) / Floating / Digital
X5-HV
(ON/OFF); 100-240 VAC (same
307: X5-OCV,
as device power supply)
X5-CV,
- 0.5 A continuous
X5-OHV,
- 1 A at 15% duty cycle for 10 min
X5-CHV
- Inrush current 3.0 A max (< 20 ms)
Powered
Digital (Typically Fan Speeds);
Relay
- 100-240 VAC (same as device
Outputs:
power supply);
X2-LOW,
- 3.0 A max. (inductive or resistive
X2-MED,
load) for the total sum of outputs;
X2-HIGH
Normally Open Contacts;
All share the same common;
Digital Relay
Digital (Typically Electric Heater)
Contact
/ Dry contact (100 to 255 VAC);
207: X3-EH1,
207: 9.0 A max. on a resistive
X3-EH2
load (2 kW at 230 VAC);
307: X3-EH1,
307: 6.0 A max. on a resistive
X3-EH2, X4-
load (1.4 kW at 230 VAC);
LV1, X4-LV2
Normally Open Contacts;
Digital dedicated common;
Analogue
Linear (0-10VDC)
207: X6-ECF
- 5 mA max.
307: X6-ECF,
X6-AD
5