Herunterladen Inhalt Inhalt Diese Seite drucken

Setup The Ups - PowerWalker VFI 1000 Bedienungsanleitung

Online ups
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 21
2‐2. Setup the UPS 
Step 1: UPS input connection 
Plug the UPS into a two‐pole, three‐wire, grounded receptacle only. Avoid using extension cords.   
For 208/220/230/240VAC models: The power cord is supplied in the UPS package.   
For 110/115/120/127VAC models: The power cord is attached to the UPS. The input plug is a 
NEMA 5‐15P for 1000, 1000L, 1500 and 1500L models, NEMA 5‐20P for 2000 and 2000L models.     
Note: For Low voltage models: Check if the site wiring fault indicator lights up in LCD panel. It will be 
illuminated  when  the  UPS  is  plugged  into  an  improperly  wired  utility  power  outlet  (Refer  to 
Troubleshooting section). 
 
Step 2: UPS output connection 
For socket‐type outputs, there two kinds of outputs: programmable outlets and general outlets. 
Please connect non‐critical devices to the programmable outlets and critical devices to the 
general outlets. During power failure, you may extend the backup time to critical devices by 
setting shorter backup time for non‐critical devices.   
For terminal‐type input or outputs, please follow below steps for the wiring configuration: 
a) Remove the small cover of the terminal block 
b) Suggest using AWG14 or 2.1mm
power cords for NEMA type. 
c) Upon completion of the wiring configuration, please check whether the wires are securely 
affixed. 
d) Put the small cover back to the rear panel. 
 
Step 3: Communication connection 
Communication port: 
USB port                            RS‐232 port                  Intelligent slot 
 
To allow for unattended UPS shutdown/start‐up and status monitoring, connect the communication 
cable one end to the USB/RS‐232 port and the other to the communication port of your PC. With the 
monitoring software installed, you can schedule UPS shutdown/start‐up and monitor UPS status 
through PC. 
 
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing 
either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring 
options.   
PS. USB port and RS‐232 port can't work at the same time.   
 
Step 4: Network connection 
Network/Fax/Phone surge port 
Connect a single modem/phone/fax line into surge‐protected "IN" outlet on the back panel of the 
UPS unit. Connect from "OUT" outlet to the equipment with another modem/fax/phone line cable. 
 
 
www.powerwalker.com 
2
 power cords. Suggest using WG12‐10 or 3.3mm
 
 
Page 5
2
‐5.3mm
 
EN
2
 

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Vfi 1500Vfi 2000Vfi 3000

Inhaltsverzeichnis