Herunterladen Inhalt Inhalt Diese Seite drucken

Troubleshooting - PowerWalker VFI 1000 Bedienungsanleitung

Online ups
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 21
 
4. Troubleshooting 
If the UPS system does not operate correctly, please solve the problem by using the table below.   
Symptom 
No indication and alarm even 
though the mains is normal.   
The icon 
and the warning code 
  flashing on LCD display and 
alarm is sounding every second. 
The icon 
and 
LCD display and alarm is sounding 
every second. 
The icon 
and 
LCD display and alarm is sounding 
every second. 
Fault code is shown as 27 and the 
icon 
  is lighting on LCD 
display and alarm is continuously 
sounding. 
Fault code is shown as 28 and the 
icon 
  is lighting on LCD 
display and alarm is continuously 
sounding. 
The icon 
  and
flashing on LCD display and alarm is 
sounding twice every second. 
Fault code is shown as 43 and The 
icon 
  is lighting on LCD 
display and alarm is continuously 
sounding. 
 
www.powerwalker.com 
The  AC  input  power  is  not 
connected well. 
The AC input is connected to 
the UPS output. 
EPO function is activated. 
Line and neutral conductors 
  flashing on 
of UPS input are reversed. 
The external or internal 
  flashing on 
battery is incorrectly 
connected. 
Battery voltage is too high or 
the charger is fault. 
Battery voltage is too low or 
the charger is fault. 
UPS is overload   
is 
UPS is overloaded. Devices 
connected to the UPS are fed 
directly by the electrical 
network via the Bypass. 
After repetitive overloads, 
the UPS is locked in the 
Bypass mode. Connected 
devices are fed directly by 
the mains. 
The UPS shut down 
automatically because of 
overload at the UPS output. 
Possible cause 
Page 15
Remedy 
Check  if  input  power  cord 
firmly  connected  to  the 
mains.   
Plug  AC  input  power  cord  to 
AC input correctly.   
Set  the  circuit  in  closed 
position  to  disable  EPO 
function. 
Rotate  mains  power  socket 
by 180° and then connect to 
UPS system. 
Check  if  all  batteries  are 
connected well. 
Contact your dealer. 
Contact your dealer. 
Remove  excess  loads  from 
UPS output. 
Remove  excess  loads  from 
UPS output. 
Remove  excess  loads  from 
UPS  output  first.  Then  shut 
down the UPS and restart it. 
Remove  excess  loads  from 
UPS output and restart it. 
EN

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Vfi 1500Vfi 2000Vfi 3000

Inhaltsverzeichnis