Herunterladen Inhalt Inhalt Diese Seite drucken

Conditions Of Safe Use - Eaton Xenon beacon XB15 Technische Anleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 22
Xenon beacon XB15
English

Conditions of safe use:

The following conditions apply to the installation,
operation and maintenance of the XB15. Failure to
observe these may compromise the safety integrity of the
Beacon.
1.
The user shall comply with the requirements given in
this Safety manual in regard to all relevant functional
safety aspects such as application of use, installation,
operation, maintenance, proof tests, maximum
ratings, environmental conditions, repair, etc.
2.
If the Beacon is to be used on a Fire Alarm system it
is recommended as per BS 5839 part 1 (eq. EN 54),
that the product is tested at least once a week. In all
other applications it is strongly recommended to test
the product at least once a year.
8
8
Xenon beacon Xb15 TM250 Issue F October 2019 www.eaton.com
3.
Selection of this equipment for use in safety
functions and the installation, configuration, overall
validation, maintenance and repair shall only be
carried out by competent personnel, observing all the
manufacturer's conditions and recommendations in
the user documentation.
4.
All information associated with any field failures
of this product should be collected under a
dependability management process (e.g., IEC
60300-3-2) and reported to the manufacturer.
5.
If the product is used in a redundant installation,
both hardware safety integrity and systematic safety
integrity for SIL 2 can be achieved. The installation
must be such as to ensure sufficient protection
against common cause failures and independence
from cascading failures.