Xenon beacon XB15
English
The telephone initiate versions of the Beacon are not
included in this safety manual.
Under No fault (Normal) Operating conditions the XB15
Beacon will provide a spherical visual warning light when
required by the system.
Under fault conditions the failure mode of the Beacon is a
failure to provide a spherical visual warning light. For the
failure rate associated with this failure mode please refer
to the table below.
'To provide a spherical cycled visual warning light when energized'.
Summary of Clauses
2/7.4.2 and 2/7.4.4
Architectural constraints
Safe Failure Fraction (SFF)
λ
Random hardware
λ
failures: [h
]
-1
λ
Random hardware
λ
failures: [h
]
-1
Diagnostic coverage (DC)
PFD @ PTI = 730Hrs, MTTR = 8 Hrs
Average freq. of dangerous failure (high
demand-PFH)[h
]
-1
Hardware safety integrity compliance
Systematic safety integrity compliance
Systematic Capability
(SC1, SC2, SC3, SC4)
Hardware safety integrity achieved
Assessment of functional safety – XB15 AC
This Beacon is intended for use in a safety system
conforming to the requirements of IEC61508. UL has
conducted a Failure Modes Effect and Diagnostic
6
6
Xenon beacon Xb15 TM250 Issue F October 2019 www.eaton.com
Safety function:
XB15 Xenon Beacon
Single Mode (1oo1)
HFT=0
62%
0.00E+00
DD
5.85E-06
DU
0.00E+00
SD
9.53E-06
SU
0.00%
2.18E-03
5.85E-06
[
Limited to: SIL 1 (1oo1) & SIL 2 (1oo2) due to SFF value.
Assessment of functional safety – XB15 DC
This Beacon is intended for use in a safety system
conforming to the requirements of IEC61508. Sira Test
& certification Ltd has conducted a Failure Modes Effect
and Diagnostic Analysis (FMEDA) of the DC version of
XB15 Xenon Beacon against the requirements of IEC
61508-2 using a Proof Test Interval of 730hrs.
The results are shown below and are based on Route 1H.
The Beacon is classed as a Type B device.
Xb15 Dc beacon
XB15 Xenon Beacon
Redundant Mode (1oo2)
HFT=1
62%
0.00E+00
5.85E-07
0.00E+00
9.53E-07
0.00%
2.18E-04
5.85E-07
Route 1
H
See report R56A24816B
SC2 (R56A24816B)
Analysis (FMEDA) of the XB15 Xenon Beacon against the
requirements of IEC 61508-2 using a Proof Test Interval of
8760hrs.
The results are shown below and are based on Route 1
The Beacon is classed as a Type B device.
Verdict
Type B
SIL 1
SIL 2 (1oo1)
SIL 1 (1oo1)
.