English

Removing/replacing xenon tube

Unscrew the grub screw (2.0mm A/F hexagon key) in the
flange of the cover 3 full turns (Do not fully unscrew).
Unscrew and remove the cover and lens assembly using
the spanner supplied to gain access to the inside of
the unit.
Remove the old tube by unscrewing the terminal block
fixings. The replacement tube can now be fitted (see
xenon tube installation sheet, which is supplied with the
replacement tubes).
Once the new tube has been correctly fitted, replace the
cover assembly, ensuring the cover is fully screwed down.
There should be a maximum gap of 0.2mm between
the faces of the cover and enclosure to ensure o-ring
compression. Ensure the cover seal is correctly seated in
its groove during re-assembly. Re-tighten the grub screw
(2.0mm A/F hexagon key) in the cover flange to secure
the cover.

6.0 Special conditions for safe use

1.
Painting and other surface finishes, other than those
applied by the manufacturer, are not permitted.
2.
In order to maintain the dust tight integrity of the
enclosures (IP6X), the threads of cable entry devices
and stopping plugs shall be sealed in accordance
with the applicable code of practice for flameproof
installation.

7.0 Certification/approvals

IECEx units

Certified to IEC 60079-0, IEC 60079-1, IEC60079-28,
IEC60079-31
Ex d unit (IEC certification No. IECEx BAS 05.0048X)
Ex db op is IIC T
Gb
G
Ex tb op is IIIC T
Db IP66/67
D
T
amb.
Tube Energy
T-rating (T
G
T4
15J
T5
T4
10J
T5
T6
T5
5J
T6
The IECEx certificate and product label carry the IECEx
equipment protection level marking
Gb
Db
Where Gb signifies suitability for use in a Zone 1 surface
industries area in the presence of gas.
Where Db signifies suitability for use in a Zone 21 surface
industries area in the presence of dust.
4
4
Xenon beacon Xb15 TM250 Issue F October 2019 www.eaton.com
)
T-rating (T
)
T
D
amb.
T135°C
(-55°C to +70°C)
T100°C
(-55°C to +40°C)
T135°C
(-55°C to +70°C)
T100°C
(-55°C to +55°C)
T85°C
(-55°C to +40°C)
T100°C
(-55°C to +70°C)
T85°C
(-55°C to +55°C)

ATEX units

Certified to EN 60079-0, EN60079-1, EN 60079-28,
EN 60079-31
Ex d unit (ATEX certification No. Baseefa04ATEX0009X)
Ex db op is IIC T
Gb
G
Ex tb op is IIIC T
Db IP66/67
D
T
amb.
Tube Energy
T-rating (T
G
T4
15J
T5
T4
10J
T5
T6
T5
5J
T6
The ATEX certificate and product label carry the ATEX
group and category marking:
II 2 GD
Where:
Signifies compliance with ATEX
II
Signifies suitability for use in surface industries
2
Signifies suitability for use in a zone 1 area
G
Signifies suitability for use in the presence of gases
D
Signifies suitability for use in the presence of dust
EN54-23:2010 visual alarm device – beacon
XB15 (24Vdc units only)
Rating 21.6v- 26.4v DC Absolute. Amps 0.99
Environment Type B Outdoor applications
IP code (IP33C) to BS EN 60529:1992
The Red lens Beacon is supplied with the following
LPCB markings.
The White lens Beacon is supplied with the following
LPCB markings.
This signifies unit compliance to the relevant European
directives, in this case 89/106/EEC, along with the name
and number of the notified body issuing the certificate
of conformity.
)
T-rating (T
)
T
D
amb.
T135°C
(-55°C to +70°C)
T100°C
(-55°C to +40°C)
T135°C
(-55°C to +70°C)
T100°C
(-55°C to +55°C)
T85°C
(-55°C to +40°C)
T100°C
(-55°C to +70°C)
T85°C
(-55°C to +55°C)