Herunterladen Inhalt Inhalt Diese Seite drucken

Assessment Of Functional Safety; Conditions Of Safe Use - Eaton SM87HXB Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 18
The safety function of the Beacon is to provide an inter-
mittent spherical visual warning light when the correct
voltage is applied to the unit. The DC versions of the
Beacon are designed to operate on a supply voltage
tolerance of +/- 20%; the AC versions of the beacon are
designed to operate on a supply voltage tolerance of
+/- 10%.
The telephone initiate versions of the Beacon are not
included in this safety manual.
Under No fault (Normal) Operating conditions the
SM87HXB Beacon will provide a spherical visual warning
light when required by the system.
Under fault conditions the failure mode of the Beacon is a
failure to provide a spherical visual warning light. For the
failure rate associated with this failure mode please refer
to the table below.

Assessment of functional safety

The SM87HXB Call Point is intended for use in a safety
system conforming to the requirements of IEC61508.
UL has conducted a Failure Modes Effect and Diagnostic
Analysis (FMEDA) of the SM87HXB Beacon against the
requirements of IEC61508-2 using a proof test interval of
8760hrs.

Conditions of safe use

The following conditions apply to the installation, operation
and maintenance of the assessed equipment. Failure to
observe these may compromise the safety integrity of the
assessed equipment.
1. The user shall comply with the requirements given in
the manufacturer's user documentation (This Safety
Manual and Technical manual) in regard to all relevant
functional safety aspects such as application of use,
installation, operation, maintenance, proof tests,
maximum ratings, environmental conditions, repair, etc;
Xenon beacon - SM87HXb & SM87XbT- drafT 1 TM001 Issue J February 2023 www.eaton.com
Xenon beacon - SM87HXB & SM87XBT
The results are shown below and are based on Route 1
The Beacon is classed as a Type A device.
SM87HXb beacon
Safety Function of SM87HXB Beacon:
'To provide a spherical cycled visual warning light when energised'
Architectural
Type A
constraints:
HFT=0
SFF= 73%
Random hardware
λ
= 0
DD
failures:
λ
= 2.96E-07
DU
Probability of failure
PFD
=1.30E-03
AVG
on demand:
(Low Demand Mode)
Probability of
PFH = 2.96E-07
Dangerous failure on
(High Demand
safety function:
Mode)
Hardware safety
integrity compliance
Systematic safety
integrity compliance
Systematic Capability
Overall SIL-capability
achieved
2. Selection of this equipment for use in safety functions
and the installation, configuration overall validation,
maintenance and repair shall only be carried out by
competent personnel, observing all the manufacturer's
conditions and recommendations in the user
documentation.
3. All information associated with any field failures
of this product should be collected under a
dependability management process (e.g., IEC
60300-3-2) and reported to the manufacturer.
4. The unit should be tested at regular intervals to
identify any malfunctions; in accordance with this
safety manual.
English
H
Proof Test Interval
SIL2
=8760Hrs
MTTR = 8 Hrs
λ
= 0
SD
λ
= 8.12E-07
SU
SIL2
SIL2
Route 1
H
Route 1
S
SC2
SIL 2 (Low Demand)
SIL 2 (High Demand)
3

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Sm87xbt

Inhaltsverzeichnis