passing through p1), and QL. After tout has expired, "DONE" appears in the up-
per status bar, and the values for dP, dT, and QL appear alternately in the lower
status bar.
Press the center button to acknowledge the message and return the sensor to
u
measurement readiness.
Supply pressure p0 > p1 and values below p1 and p2 before reaching tout
If the upper pressure value P1 is not reached after the start of the measurement,
measurement of dT starts. "MEAS" then appears in the upper status bar. In the
lower status bar, the display alternates between the values for dP (pressure differ-
ence between p1 and p2), dT (time period in seconds since passing through p1
until reaching p2), and QL. If the value falls below the lower (pressure) threshold
P2, the display color changes from green to red.
There is a leak. Fig. 23 shows a schematic depiction of the leakage measurement.
"DONE" appears in the upper status bar, and the values for dP, dT, and QL appear
alternately in the lower status bar.
Press the center button to acknowledge the message and return the sensor to
u
measurement readiness.

9 Service and Maintenance

The device is maintenance-free.
Only use water and, if necessary, a mild cleaning agent for cleaning.
u

10 Disassembly and Exchange

System is under high pressure!
Danger of injury and system damage from uncontrolled system operating
states.
Make sure that the system component in which the pressure sensor is in-
u
stalled is not under pressure or voltage before beginning disassembly.
1. Make sure that the system is not under voltage or pressure.
2. Loosen and remove all connections.
3. Loosen the pressure sensor from the (threaded) pressure connection using a
wrench, or pull the pressure sensor straight out of the push-in fitting.
4. Dispose of the packaging and used parts in accordance with the regulations of
the country where used.

11 Error and Warning Messages

The display areas A and B blink in case of error and warning messages (Fig. 2).
Display
Cause
OL OVERPRESS
Applied pressure > end of
measuring range
UL UNDERPRES
Applied pressure < start of
the measuring range
ERR1 GEN.ERROR
General error
ERR2 SHORTOUT1
Short-circuit present at
output 1
ERR2 SHORTOUT2
Short-circuit present at
output 2
ERR3 OVERVOLTG
Supply voltage > 30 V DC
ERR4 LOW VOLTG
Supply voltage < 17 V DC
ATT1 SHIFT RP1
The switching point is set
below the existing reset-
ATT1 SHIFT RP2
ting point. The resetting
point is automatically set
with the smallest possible
hysteresis below the new
switching point.
AVENTICS
TM
PE5 | R412010843-BAL-001-AF | English
CAUTION
Remedy
Set the pressure within
the measuring range (see
Figs. 21 and 22)
Contact us!
Rectify short-circuit and
disconnect the supply
voltage temporarily so
that the output returns to
normal operation.
1)
Correct the setting of the
supply voltage
1)
Press the center button to
acknowledge the mes-
sage
Display
Cause
ATT2 ADJ>LIMIT
During zero point adjust-
ment, the applied pres-
sure is outside the permis-
sible limit of 5% of the
range.
LOCK KEYLOCKED
If the key lock is active,
the system will attempt
to go into the program-
ming mode.
WARN (p<p1)
The value for p0 is not at
least 0.02 bar higher than
the upper threshold value
p1.
1)
The outputs switch off if the supply voltage exceeds 30 V DC or falls below
17 V DC.
If a second switch output is present, you can configure it as a diagnostic output.
In the extended programming functions (EF), select the value "DIA" for the
u
parameter "OUT2" (see "Selecting the extended programming functions").
The diagnostic output and the digital outputs behave as follows in case of an er-
ror:
Display
Digital outputs
(area A)
PNP
NPN
mode
mode
OL
Normal function
UL
ERR1
Low
High
ERR2
Only pull-
Only pull-
down
up
ERR3
ERR4

12 Technical Data

General data
Dimensions (W x H x D)
Weight
Display
System pressure display
Update of the display
Protection class acc. to IEC 60529
Measuring ranges
Operating temperature range
Storage temperature range
Relative humidity
Shock load
Vibration load
Materials
Port
Remedy
Press the center button to
acknowledge the mes-
sage
Enter password
Press the center button to
acknowledge the mes-
sage
Diagnostic output
Push-pull
PNP
NPN
mode
mode
mode
Low
High
Only pull-
Only pull-
down
up
Low
Low
High
Only pull-
Only pull-
Only pull-
down
down
up
35 mm x 63 mm x 35 mm
Approx. 45 g
LCD, 4-digit, backlit
Selectable: bar, MPa, kPa, psi and inHg
Settable: 1000, 500, 200, and 100 ms
IP65/67 with assembled connection
ports
–1 to 0 bar
0 to +10 bar
–1 to +1 bar
–1 to +10 bar
0 to +6 bar
0 to +12 bar
0 to 60°C
-20 to 80°C
< 90%
Max. 30 g, xyz, DIN EN 60068-2-27
(11 ms, mechanical shock)
Max. 5 g, xyz acc. to IEC 60068-2-6
(10 to 150 Hz, vibration at resonance)
Housing: polycarbonate
Buttons: TPE
Mounting clip: POM
Seals: NBR
M12x1, 4-pin:
(outputs 2x digital and outputs 1x ana-
log and 1x digital)
5-pin:
(outputs 2x digital, 1x analog, leakage
mode: outputs 1x digital, 1x analog, in-
put 1x digital)
Push-pull
mode
Low
NPN ac-
tive
Low NPN
Pull-down
22