DAB E1GI Installations- Und Wartungsanleitungen Seite 46

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 54
16.
Table of PARAMETERS to be set in the "PUMPS CONTROLLER" CONTROL UNIT ONLY
Number of Pages
Parameter
Insert Key
1. Language
5. PumpsAntiblock
1: ON / 2: OFF
6. AntiblockTime
8. Rtd.Pump Pres.
9. SetPoint Pres.
10. Dif. Start/Stop P1
11. Dif.Start P2P3P4
12. Dif.Stop P2P3P4
13. DelayStart P1
14. DelayStart P2P3P4
15. Min.Run Pilot
16. Min.Run P2P3P4
17. Cnt.Strt.Pilot
FOR DAB SERVICE (DAB STANDARD KEY)
Description
Insert DAB STANDARD KEY
Languages in which the parameters are written:
Italian = 0
English = 2
French = 3
German = 4
Spanish = 5
Choice whether to exclude or insert the pump
anti-blocking test cycle.
Setting of the pump stopped time after which the
pump anti-blocking test must be carried out.
Rated pump pressure with the circuit at flow-
rate zero.
Mean pressure to be maintained in the system.
The increase or decrease of the SetPoint
pressure modifies all the start and stop values
of each pump making them higher or lower
(see graph ref.18).
Pressure difference allowed between the start
and stop of the PILOT pump or P1 SUPPLY
pump.
Lower pressure differential for starting between
the first pump and the second pump, between the
second and the third, between the third and the
fourth (whether they are pilot, supply or backup).
Upper pressure differential for stopping between
the first pump and the second pump, between the
second and the third, between the third and the
fourth (whether they are pilot, supply or backup).
Delay time at start of the PILOT pump or P1
SUPPLY pump, when the pressure is lower than
the parameter set in Dif.Start/Stop P1
Delay time at start of the SUPPLY pumps P2, P3,
P4 when the pressure is lower than the parameter
set in Dif.StartP2P3P4.
Choice of the minimum running time of the
PILOT pump or SUPPLY pump P1.
Choice of the minimum running time of the
SUPPLY pumps P2, P3, P4 or of the BACKUP
pump.
Choice of the minimum time within which the
second start, after the first, is NOT allowed for the
PILOT pump or the SUPPLY pump P1. Any
intervention keeps the pump blocked until the end
of the set time. In this interval of time the pump
start delay is indicated with the message WAIT.
ENGLISH
44
Field
Unit of
measure
0-:-99999
value
0-:-5
value
1-:-2
value
1-:-255
day
0,00-:-25,5
bar
0,00-:-25,5
bar
0,00-:-2,00
bar
0,00-:-1,00
bar
0,00-:-1,00
bar
0-:-20
sec.
0-:-20
sec.
0-:-20
sec.
0-:-20
sec.
0-:-600
sec.
continued on the next page
DAB
Standard
SetUp
10009
2: English
2
7
0,00
0,00
1,00
0,3
0,2
0
1
0
2
10