Herunterladen Inhalt Inhalt Diese Seite drucken

Maintenance And Cleaning; Technical Data - VOLTCRAFT VC-63 SE Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

RCD TEST (RC OR RESIDUAL CURRENT PROTECTIVE DEVICES
(RCD) TEST)
The voltage tester can be used to check whether the RC works properly.
The voltage tester can only check whether the residual current protective device is
working properly. The testing or triggering current as well as the triggering time cannot be
determined any longer!
Connect the measuring probe (2) with the protective conductor and the measuring probe (3) with
the phase.
Now, press the red (12) button and the red (12a) button simultaneously.
MEASURING POINT LIGHTING
The measurement device has LED illumination on the outside of the case in order to allow measure-
ments when there is little light. To activate this feature press on the button (13). The LED switches
off automatically after roughly 30 seconds off to save battery power.

MAINTENANCE AND CLEANING

Apart from the occasional battery change, the product is maintenance-free for you.
However, in order to ensure the accuracy of the measurement device over a long period, it is
recommended to have the device calibrated once a year.
Never clean the product while it is connected to a voltage source. Use a clean, dry, soft cloth for
cleaning. Do not use aggressive cleaning agents as these can cause discolouration. To prevent
scratch marks, do not press too strongly on the surface when cleaning.
DISPOSAL
a) General instructions
Please dispose of the unserviceable product according to the relevant statutory require-
ments. Remove any inserted battery and dispose of it separately from the product.
b) Batteries
You as the ultimate consumer are legally obliged (Regulation on Spent Batteries) to return all dead
batteries and accumulators. Disposal in the household waste is prohibited.
Batteries containing hazardous substances are labelled with the symbol opposite indicat-
ing that disposal in the domestic waste is forbidden. The symbols of the critical heavy
metals are: Cd = Cadmium, Hg = Mercury, Pb = Lead.
You can return your used batteries/rechargeable batteries free of charge to the official collection
points in your municipality, in our stores, or anywhere batteries or rechargeable batteries are sold.

TECHNICAL DATA

Voltage range ............................................................12 - 690 V (DC/AC)
Frequency range .......................................................0 Hz; 16 - 400 Hz
LED resolution ...........................................................+/-12, 24, 36, 50, 120, 230, 400, 690 V
Measurement tolerance for the voltage test ..............+/- (3% + 5 Digit)
DC/AC voltage recognition ........................................automatic
Auto Power On ..........................................................>12 V (DC/AC)
Response time ...........................................................<1 s
Max testing time (RCD test) ......................................30 s
Regeneration time (RCD test) ...................................240 s
Max. testing current ( RCD test) ...............................30 mA/230 V
Max. current w/out RCD burden ................................<3.5 mA/690 V
Measurement category ..............................................CAT IV 600 V/CAT III 1000 V
Norms ........................................................................EN 610529 and EN 61243-3:2014
Protection type ...........................................................IP64
Contamination level ...................................................2
Temperature range ....................................................-15 °C to +45 °C
Humidity .....................................................................max. 85% relative humidity, non condensing
Altitude above sea level .............................................max. 2000 m
Length of measuring cables ......................................ca. 93 cm
Power supply .............................................................2x AAA / micro batteries
Weight .......................................................................130 g
Dimensions ................................................................67 x 205 x 27 mm (W x H x D)
CONTINUITY TEST
Indication
Test current
Overvoltage protection
optic and acoustic (<400 kΩ+50%)
<5 uA
690 V (DC/AC)
This is a publication by Conrad Electronic SE, Klaus-Conrad-Str. 1, D-92240 Hirschau (www.conrad.com).
All rights including translation reserved. Reproduction by any method, e.g. photocopy, microfilming, or the capture in
electronic data processing systems require the prior written approval by the editor. Reprinting, also in part, is prohibited.
This publication represent the technical status at the time of printing.
© Copyright 2019 by Conrad Electronic SE.
2139579_V1_0719_01_dh_m_4L

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis