Nibe HPAC S40 Installateurhandbuch Seite 31

Klimamodul
Vorschau ausblenden Andere Handbücher für HPAC S40:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

MENU 7.1.2.2 - PUMP SPEED HEATING
MEDIUM GP1
Make settings here for the heating medium pump's
speed in the current operating mode, for example in
heating or hot water operation. Which operating modes
can be changed depends on which accessories are
connected.
Active cooling, auto
Alternative: on/off
Active cooling, manual
Setting range: 1 - 100 %
Passive cooling, auto
Alternative: On/Off
Passive cooling, manual
Setting range: 1 - 100 %
Minimum permitted speed
Setting range: 1 - 50 %
Speed in standby mode
Setting range: 1 - 100 %
Speed during active cooling
Setting range: 1 - 100 %
Highest permitted speed
Setting range: 50- 100%
Active cooling, auto: Here, you set whether the heating
medium pump is to be regulated automatically or
manually.
Active cooling, manual: If you have opted to control the
heating medium pump manually, you set the desired
pump speed here.
Passive cooling, auto: Here, you set whether the heating
medium pump is to be regulated automatically or
manually.
Passive cooling, manual: If you have opted to control
the heating medium pump manually, you set the desired
pump speed here.
Minimum permitted speed: Here you can restrict the
pump speed so that the heating medium pump is not
allowed to operate at a lower speed than the set value.
Speed in standby mode: The speed the heating medium
pump is to have in standby mode is set here. Standby
mode occurs when heating or cooling operation is per-
mitted at the same time as there is no need for either
compressor operation or electric additional heat.
Maximum permitted speed: Here you can restrict the
pump speed so that the heating medium pump is not
allowed to operate at a higher speed than the set value.
MENU 7.1.2.7 - PUMP SPEED BRINE
Make settings for the brine pump's speed here.
HPAC S40 | GB
Operating status
Setting range: Fixed delta, Auto, manual
Manual
Setting range: 1 - 100 %
Speed during active cooling
Setting range: 1 - 100 %
Delta-T cooling
Setting range: 2 - 10 °C
Speed in passive cooling
Setting range: 1 - 100 %
Speed in standby mode, cooling
Setting range: 0 - 100 %
Operating mode: Here you set whether the brine pump
is to be regulated automatically, manually or with fixed
delta.
Fixed delta: Here you set whether the brine pump will
be controlled with fixed delta, e.g. for ground water
systems.
Manual: If you have opted to control the brine pump
manually, you set the desired pump speed here.
Speed during active cooling: Here, you set the speed at
which the brine pump is to operate during active cooling.
Speed in passive cooling: Here you set the speed at
which the brine pump is to operate during passive
cooling.
Speed in standby mode, cooling: Here, you set the
speed at which the brine pump is to operate in standby
mode when passive cooling is permitted.
Speed in standby mode: The speed the brine pump is
to have in standby mode is set here. Standby mode oc-
curs when active cooling is permitted at the same time
as there is no need for compressor operation.
31