FITTING REMOTE PANEL (optional)
a)
Remove side screws and lift off front cover.
b)
Fix back plate to wall using pre drilled holes taking care to keep panel in a
vertical position
c)
Replace front cover (operation (a) reversed)
d)
Run interconnecting cable back to main panel taking care not to bundle it
with other system cables
WARNING : Max. distance for remote panel cable is 10 m; for longer
distances a "long distance" module (optional) must be used.
ELECTRICAL CONNECTION
To ensure correct electrical connection proceed as follows :-
1)
Ensure that the mains supply voltage corresponds to the voltage indicated on the
serial number plate. Acceptable tolerance is +/-10% of the nominal voltage.
2)
Connection to the mains supply should be made using a residual current circuit
breaker and by a qualified technician.
3)
The use of a door microswitch (not supplied) on the coldroom door is
recommended. It will automatically enable the following on each door opening:-
-lighting of room lamp, unit stop
-exclusion of temperature alarm (for 1 hour after door closure)
4)
To access the electrical panel, it is necessary to remove the unit front cover (fig. 7).
76-504-0914
16