2. Charging procedures – Three phase compressors
The fundamental procedure is the same as for single phase models but the compressor can run in the wrong direction on
starting. If this happens reverse any two phases and start again. Short term reverse rotation will not damage the compressor.
All Specter compressors (Model: ZR90 to ZR19M) have internal discharge temperature protectors which are very effective
in preventing dangerously high discharge temperatures during charging. The protection module will trip and lock the
compressor out for 30 minutes. It is not normally necessary to wait 30 minutes for the module to reset. When the compressor
has cooled down the module can be reset by breaking the power supply to the control circuit. Very often the serviceman
does not understand why the module tripped and uses a jumper wire to bypass it. He continues to charge the system and
removes the jumper when charging is complete. The compressor may or may not run with the protector back in the circuit
but it is certain that the compressor has been damaged and premature failure is inevitable.
Remote Control
When there is infrared remote control operating signal, the signal receiver on indoor unit will made a <beep> for signal
acceptance confirmation.
FAULTY INDICATION
Room/outdoor coil sensor
missing
Indoor coil sensor missing
Compressor overload
Gas leak
Pump fault
Outdoor defrost
Ensure that:
1) The unit has been mounted solidly and rigid in position.
2) Piping and connections are leak proof after charging.
3) Proper wiring has been installed.
Drainage check:
– Pour some water into the main drain pipe from the flexible drain hose.
Test run:
1) Conduct a test run after water drainage test and gas leakage test.
2) Check the following items:
a. Is the electric plug firmly inserted into the socket ?
b. Is there any abnormal sound from the unit ?
c. Is there any abnormal vibration on the unit itself or piping ?
d. Is the drainage of water smooth ?
Confirm that:
1) Condenser fan is running, with warm air blowing off the condensing unit.
2) Evaporator blower is running and discharge cool air.
3) The remote control incorporate a 3 minute delay in the circuit. Thus, it requires about 3 minutes before the outdoor
condensing unit can start up.
There are many ways of charging liquid in a "controlled manner" into the suction
side:-
1. Use valve A on the manifold gauge set
2. Use the valve on the refrigerant cylinder
3. Charge through a Shredder valve
4. Use a hose with a Shredder valve depressor
5. Charge into the suction side at some distance from the compressor
6. All of the above

INDICATOR LIGHTS

POWER
Blinks 4 times with 1 second interval
follow by 3 seconds interval
Blinks 4 times with 1 second interval
follow by 3 seconds interval
Blinks with 1 second interval
Blinks 3 times with 1 second interval
follow by 3 seconds interval
Blinks 2 times with 1 second interval
follow by 3 seconds interval

OVERALL CHECKING

LED
SLEEP
Blinks with 1
second interval
1-12
ACTION
HEAT
Call your dealer
Blinks with 1
second interval