  • DEUTSCH, seite 99
maximum loads that can be driven by the analog output:
*
output type
0-1 V
0-5 V
0-10 V
0-20 mA
4-20 mA
Probe*
Range
NTC
-50...110°C
PTC
-55...150°C
Pt1000
-200...800°C
TcJ
-40...760°C
TcK
-40...1350°C
Pt100
-200...800°C
0 ... 1V
0 ... 5V
V-I***
0 ... 10V
0 ... 20mA
4 ... 20mA
*
Important! Check the availability of the probes and models.
** The accuracy values shown are valid for an ambient temperature of 25°C
*** The maximum load on the +12V sensor power supply is 60mA
MAX LOADS TABLE
permissible load
20mA with minimum load impedance 50 Ohm
20mA with minimum load impedance 250 Ohm
20mA with minimum load impedance 500 Ohm
350 Ohm
350 Ohm
PROBES TABLE
Probe error limits
Resolution
-55...115°C
0.1°C (0.1°F)
-60...155°C
0.1°C (0.1°F)
-210...810°C
-50...770°C
0.6°C (0.7°F)
-50...1360°C
0.6°C (0.7°F)
-210...810°C
0.1°C (0.2°F)
-1 ... 10%
1 digit with ndt=0
-0.20 ... 10%
0.1 digit with ndt=1
-0.10 ... 3%
0.01 digit with ndt=2
0.05 ... 5%
0.001 digit with ndt=3
-6.25 ... 6.25%
0.2°F
0.5% end of scale + 1 digit (over entire scale)
0.2% end of scale + 1 digit (-150...300°C)
Accuracy**
0.5% full scale + 1 digit
0.5% full scale + 1 digit
0.5% full scale + 1 digit
0.4% full scale + 1 digit
0.5% full scale + 1 digit
0.5% full scale + 1 digit