PAR. DESCRIPTION
Start delay. The indicated time must elapse between the request for activation of
dn1
the controller relay and switch-on.
Delay time after switch-off. The indicated time must elapse between deactivation
do1
of the controller 1 relay and the next switch-on.
Time lag between starts. The indicated time must elapse between two consecutive
di1
starts of controller 1.
Switch-off delay. The indicated time must elapse between the request for
dE1
deactivation of the controller 1 relay and switch-off.
NOTE: for parameters dn1, do1, di1, dE1, value 0 = not active
Controller switch-on time in the event of faulty probe.
On1
If On1 = "1" and OF1 = "0" the controller remains on continuously; if On1 = "1" and
OF1 > "0" it operates in Duty Cycle mode.
Controller switch-off time in the event of a faulty probe.
If OF1 = "1" and On1 = "0" the controller remains off continuously; if OF1 = "1" and
OF1
On1 > "0" it operates in Duty Cycle mode.
CONTROLLER 2 (Folder rE2)
Setpoint 2 Offset. Temperature value to be added algebraically to the setpoint if reduced
OS2
set enabled (Economy function). It cannot assume the value 0.
db2 Response band above SEtpoint SEt2.
Relay 1 activation differential. The service will stop when SEt2 is reached (value
dF2
read by Pb1) and restart at the (SEt2+DiF) value.
HC2 Control mode selection. "H" = Hot, "C" = Cold
HS2
Maximum value assignable to SEtpoint "SEt2"
(see the Duty Cycle diagram)
(see the Duty Cycle diagram)
U.M.
RANGE
MODEL
ALL
sec
0 ... 255
ALL
min
0 ... 255
ALL
min
0 ... 255
ALL
sec
0 ... 255
ALL
min
0 ... 255
ALL
min
0 ... 255
ALL
°C/°F -30.0 ... 30.0
°C/°F
0.0 ... 30.0
ALL
ALL
°C/°F
0.1 ... 30.0
ALL
flag
C/H
TcJ/TcK
PTC/NTC/PT1000
°C/°F
LS2 ... HdL
PT100
V/I
DR4020 DR4022
0
0
0
0
0
0
0
0
0
0
1
1
0.0
0.0
1.0
1.0
1.0
1.0
H
H
760.0
760.0
800.0
800.0
800.0
800.0
100.0
100.0