2.5
Loss of safety of device with type of protection "Intrinsic safety Ex i"
WARNING
Loss of safety of device with type of protection "Intrinsic safety Ex i"
If the device has already been operated in non-intrinsically safe circuits or the electrical specifications have not been
observed, the safety of the device is no longer ensured for use in hazardous areas. There is a danger of explosion.
● Connect the device with type of protection "Intrinsic safety" solely to an intrinsically safe circuit.
● Observe the specifications for the electrical data in the certificate and in Chapter "Technical data (Page 16)".
WARNING
Unsuitable device for the hazardous area
Danger of explosion.
● Only use equipment that is approved for use in the intended hazardous area and labelled accordingly.
3
Description
3.1
Function
The positioner facilitates the separate installation of the position displacement system. The stroke or rotary angle is
registered directly at the actuator by means of a non contacting sensor. It is therefore possible to install the controller unit at
some distance away, e.g. on an assembly pipe or similar. The positioner is wired to the position displacement system by
means of electrical cable. The positioner is connected to the actuator via one or two pneumatic lines.
Such a separate installation is useful whenever the ambient conditions at the fitting exceed the specified positioner values.
The NCS consists of a molded sensor for fixed installation and a magnet. The magnet is mounted to the spindle on linear
actuators, or to the stub shaft on part-turn actuators. The sensor housing is mounted onto the console on part-turn actuators
and to the bracket on linear actuators. The bracket can be a NAMUR type, or any other mounting bracket.
Auxiliary power is supplied to the NCS via the EMC filter module C73451-A430-D23 and EMC-compatibility is ensured at the
same time.
EMC filter module ordering options:
● Installed in the positioner; see Catalog FI 01
● For retrofitting in the positioner; Order No. C73451-A430-D23. For information on retrofitting the EMC filter module, refer
to the positioner operating instructions, chapter "Installing/Mounting".
Pneumatic line
Pneumatic line for double-action actuators
Position displacement system (10 kΩ potentiometer, or NCS)
Electrical cable
Retrofittable EMC filter module (in the positioner)
Positioner
Figure 3-1
Separate installation of the NCS and positioner
SIPART PS2 Non Contacting Sensor (NCS)
A5E00097485-08, 07/2012