EMC filter module C73451-A430-D23
Figure 5-1
Connecting the NCS to the EMC filter module
Procedure
The NCS is equipped with a shielded four-pole cable. Wire this cable to the positioner as follows:
1. Feed the four-pole NCS cable
variant. The cable bushing to be used is specified in the positioner Operating Instructions, EMC filter module section.
2. Tighten the cable bushing
3. Terminate the four-pole NCS cable
4. Place the cable clamp
5. Use the screw
to bond the cable shielding lug
positioner.
6. Grounding:
The rear steel panel of the NCS is inevitably bonded to ground potential of the system by mounting the console. This
ground connection is only functional on the condition of a low-impedance connection to ground potential of the system.
Ensure this state by measuring ground resistance. If necessary, ensure proper grounding by means of an additional
cable from the NCS to ground potential.
6
Commissioning
WARNING
Improper commissioning in hazardous areas
Device failure or danger of explosion in hazardous areas.
● Do not commission the device until it has been mounted completely and connected in accordance with the information
in Chapter "Technical specifications (Page 16)".
● Before commissioning take the effect on other devices in the system into account.
6.1
Prerequisites / default settings
● Supply electrical and pneumatic auxiliary power to the SIPART PS2 positioner. The top row of the display shows the
current sensor voltage (0 to 100%), while the "NOINI" info flashes in the bottom row. The pneumatic actuator does not
move.
● Preset for part-turn actuators:
While the valve or flaps are closed, align the North pole of the magnet with the cable; "N" in position
Mounting to the part-turn actuator (Page 9)".
● Linear actuators with a stroke range up to 14 mm do not need to be preset.
● Preset for linear actuators with a stroke range > 14 mm (0.55 inch):
The magnet for the assembly kit for linear actuators > 14 mm (0.55 inch) is fixed. The factory default alignment of the
magnet is permanent.
● Monitor the display of the positioner while adjusting the actuator to its mechanical stops by means of
positioner. Verify that the displayed values never exceed the range from P2.0 to P98.0.
Note
This condition cannot be met with slipping flaps or linear actuators that exceed the mechanical actuation limits.
● If the display shows an inverted control direction, reset parameter "YDir" to "FALL", or turn the magnet by 180° (not
available for version 6DR4004-.N.30).
SIPART PS2 Non Contacting Sensor (NCS)
A5E00097485-08, 07/2012
through the cable bushing. Note: The type of cable bushing depends on the device
.
in the positioner in accordance with the connection diagram.
onto the outer insulation of the four-pole NCS cable
Cable shielding lug
and the cable clamp
.
to equipment ground terminal of the
in "Figure 4-1
and
at the
15