21. PROGRAMMING BOARD PARAMETERS USING THE AVS 77 CLIMATE CONTROLLER

To set the boiler parameters, proceed as follows:
• press and hold down IP for at least three seconds;
• press and hold down
and then press
When the function is enabled, "OF 725" appears on the display
followed by the software version of the LMU34 board.
To modify boiler parameters, proceed as follows:
• Press +/- and
together and hold down for 3 seconds;
(this accesses the list of parameters, the display shows OF
504 alternating with the parameter itself).
• press buttons +/-
to scroll the parameters (see table be-
low);
• press buttons +/-
to modify individual parameters;
• press OK to confirm the modified parameter and return to the
list of parameters;
• press IP to exit
Summary of parameters that can be adjusted with the AVS 77 climate controller
Parameters
Description of parameters
504
Maximum heating delivery temperature (°C)
516
Automatic summer-winter switching
532
Gradient of "kt" heating curve
534
Ambient temperature offset
536
Maximum fan speed (rpm) in heating mode (max. power in heating mode)
541
Max. PWM (%) in heating mode
544
Pump post-circulation time (s)
545
Minimum burner pause time (s) in heating phase
Chimney sweep function:
555.0
1: enabled
0: disabled
Anti-legionellosis function:
555.1
1: enabled
0: disabled
555.2
Hydraulic device setting
555.3
NOT USED
AVS 77 climate controller
555.4
1: delivery temperature controlled by AVS 77, heat demand is managed by the boiler AT
0: delivery temperature and heat demand are managed independently by AVS 77 or TA.
555.5...555.7
NOT USED
608
PWM (%) setting: ignition power
609
PWM (%) setting: minimum power
610
PWM (%) setting: maximum power
611
Rpm setting: ignition power
612
Rpm setting: minimum power
613
Rpm setting: maximum power
614
OT input setting (AVS 77)
641
Post-ventilation time setting (s)
Boiler power adjustment
677
max. (100%) - min. (0%) during calibration
Tipologia caldaia (impostazione circuito idraulico)
1 : appliance for heating only
651
2 : instantaneous appliance
4 : with preheating (section 3.7.1)
*
These parameters differ depending on the model of boiler installed. See the Service instructions for a complete
list of parameters and settings.
INSTRUCTIONS FOR FITTERS
(see figure 15).
Figure 15
70
0703_0910
Default
80
30
15
0
*
*
180
180
0
1
0
-
0
0
*
*
*
*
*
*
0
10
0
*
926.420.3 - EN