The boiler parameters may only be modified by professionally qualified staff proceeding as follows:
AT
a) press the
, keys on the boiler's front panel together for about 3 s until the parameter H90 appears on
the display;
GB
b) press the
keys to select the parameter for modification;
c) press the
and
d) press the
key to exit the programming function.
The following are the parameters generally used:
Parameter N.
Description
H90
Minimum D.H.W. temperature setting (°C).
H91
D.H.W. activation program
(0=active; 1=not active)
H505
Maximum temperature (°C) of the central heating circuit HC1 corresponding to:
-
-
-
H507
Maximum temperature (°C) of the central heating circuit HC2 of a system with more than one zone,
corresponding to the circuit of the low-temperature zone if the SIEMENS AGU2.500 accessory
is used.
H516
Automatic Summer / Winter switching temperature (°C).
H532
Selection of temperature curve of central heating circuit HC1 (see Graph 1)
H533
Selection of temperature curve of central heating circuit HC2 (see Graph 1)
H536
Selection of central heating power (N. of fan rpm)
H612
Speed setting (rpm) : minimum power
H613
Speed setting (rpm) : maximum power
H544
Pump post-circulation time in central heating mode (min)
H545
Burner operating pause time between two start-ups (s)
Hydraulic system setting (see instructions provided with the SIEMENS AGU2.500 accessory)
H552
H552 = 50 with AGU2.500
Configuration of heating circuits
H553
H553 = 12 with AGU2.500
Programmable function:
H615
Configuration of system with supplementary pump
H632 = 00001111 with AGU2.500
The value of Bit could be 1 or 0.
H632
Press the keys 5 and 6 to select the bit to modify (b0 is the bit on the right, b7 is the last bit on
the left).
To modify the Bit value press on the keys 7 and 8
Fan overrun time setting (s)
H641
Setpoint of autonomous ANTILEGIONELLA function
H657
60...80 °C = setting temperature range

14. SETTING THE BOILER PARAMETERS

keys to modify the parameter;
the main circuit in systems with just one zone;
the circuit of the zone where the QAA73 room temperature control device is installed in case
of systems with more than one high-temperature zone;
the high temperature zone circuit in mixed systems and if the SIEMENS AGU2.500 accessory
is used.
0 = function inactive
INSTRUCTIONS PERTAINING TO THE INSTALLER
100
Factory setting
10
1
80
80
20
15
15
See
table
3
180
2
21
9
00001100
10
0