Temperature class
TF110 to CEN 335-2-51.
Liquid temperature
Maximum +110°C.
Continuously: +15°C to +95°C.
Pumps in domestic hot-water systems:
Continuously: +15°C to +60°C.
To avoid condensation in the terminal box and the
stator, the pumped liquid temperature must always
be higher than the ambient temperature. See the
table below:
Ambient
temperature
[°C]
Min. [°C]
15
20
25
30
35
40
System pressure
The system pressure is indicated on the pump
flanges:
Pump type
PN 6 PN 10

UPED 50-120

UPED 65-120
UPED 80-120
UPED 100-60
Inlet pressure
The following minimum pressures must be available
at the pump inlet during operation:
Pump type
UPED 50-120
UPED 65-120
UPED 80-120
UPED 100-60
146
Liquid temperature
Max. [°C]
15
110
20
110
25
110
30
110
35
90
40
70
Number
PN 6/
of bolt
PN 10
holes
4
4
4
8
4
8
Liquid temperature
75°C
90°C
[bar]
[bar]
0.4
0.7
0.9
1.2
1.6
1.9
0.95
1.25
EMC (electromagnetic compatibility)
EN 61800-3.
Sound pressure level
The sound pressure level of the pump is lower than
54 dB(A).
Leakage current
The pump mains filter will cause a discharge current
to earth during operation. I
Inputs and outputs
Start/stop input
External potential-free switch.
Contact load:
5 V, 0.1 mA.
Screened cable.
Max. curve input
Loop resistance:
Maximum 130 Ω/km.
Logical levels:
Min. curve input
Logical zero: U < 1.5 V.
Logical one: U > 4.0 V.
Input for analog
External signal: 0-10 VDC.
0-10 V signal
Maximum load: 1 mA.
Screened cable.
Signal output
Internal potential-free change-
over contact.
Maximum load:
250 V, 2 A AC1.
Minimum load: 5 V, 1 mA.
Screened cable.
Bus input
Grundfos bus protocol,
GENIbus protocol, RS-485.
Screened cable.
Lead cross section:
0.25 - 1 mm².
Cable length:
Maximum 1200 m.

11. Disposal

This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest
Grundfos company or service workshop.
< 3.5 mA.
leakage
Subject to alterations.